5.3.7 Full internal mounting of the cooling unit
First, dismantle the top and bottom louvred grilles as
well as the infill panel and the display in the same way
as for partial internal mounting (see section 5.3.6 "Par-
tial internal mounting of the cooling unit").
Cut the sealing tape in the dispatch bag to the re-
quired length so that it can be placed all the way round
the cover once.
Start sticking the sealing tape at the bottom edge, so
that the joint between the two ends of the sealing tape
is likewise on the bottom edge of the unit.
Carefully stick the sealing tape as close as possible to
the edge of the cover.
On the front top edge of the cover, push the clip in-
cluded with the supply into the relevant hole.
This clip will prevent the cooling unit from falling out of
the mounting cut-out later on before it is properly se-
cured with the threaded bolt.
Fig. 27: Clip at top edge of cover
Key
1Cover
2 Clip on the cover
Lift up the cooling unit, preferably with a lifting eye us-
ing suitable lifting gear, and insert it into the mounting
cut-out in the door or side panel of the enclosure with
the two brackets at the bottom of the cover.
If transportation by crane is not possible, lift the cool-
ing unit into the mounting cut-out in the same way us-
ing the handle.
Fig. 28: Bracket at the bottom of the cover
Key
1 Bracket in mounting cut-out
2 Outside of door
Push the cooling unit into the mounting cut-out at the
top until the clip behind the cut-out latches home.
Fig. 29: Clip at top edge of cooling unit
Key
1 Outside of enclosure door
2 Clip in mounting cut-out
Mount the corner brackets onto the top two threaded
bolts from the outside.