User manual

Rittal enclosure cooling unit 19
5 Installation
EN
Fig. 30: Corner brackets on top threaded bolts
Key
1 Threaded bolt
2Corner bracket
Mount the L-shaped brackets onto the bottom two
threaded bolts from the outside.
Fig. 31: L-shaped brackets on bottom threaded bolts
Key
1 L-shaped bracket
2 Threaded bolt
Next, working from the outside of the enclosure, se-
cure the four threaded bolts in the corners of the cover
using the corresponding nuts from the dispatch bag.
Fig. 32: Mounting points on cooling unit
Key
1 Threaded bolts with nuts (4x)
2 Fastening clamps
3 Cooling unit behind enclosure door
4 Front of cooling unit (without louvred grille)
Insert the six fastening clamps into the cover of the
cooling unit.
These fastening clamps ensure that the cooling unit is
directly in contact with the mounting cut-out of the en-
closure door over the entire height.
Connect the display to the connector and fit the entire
infill panel to the cooling unit.
Place the bottom louvred grilles onto the holders and
secure the two stays of the top hinge mechanism into
the brackets attached to the cooling unit cover.
Finally, replace the top louvred grille onto the cover.
If applicable, re-attach the door or side panel including
cooling unit to the enclosure if not mounting directly on
the enclosure.
5.3.8 Connect the condensate water discharge
There is a condensate water evaporator fitted in the ex-
ternal circuit of the cooling unit. With an enclosure con-
nected, this condensate water evaporator may typically
evaporate condensate water volumes of up to 100 ml/h.
If larger quantities of condensate water are produced, a
condensate water discharge hose may additionally be
fitted. This hose allows condensate water to be routed
out of the cooling unit pressurelessly. A suitable hose is
available as an accessory from Rittal (see section 13
"Accessories").
Please follow the instructions given below: