User manual

5 Installation
EN
20 Rittal enclosure cooling unit
The hose must be laid with an adequate and constant
gradient to prevent siphoning.
The hose must be laid without any kinks.
If extended, the cross-section of the hose must not be
reduced.
The hose should be routed to a drain or external con-
densate water evaporator by the customer.
Fig. 33: Connection for condensate water discharge hose
Key
1 Connection point
2 Hole in enclosure for hose
Connect a suitable hose to the condensate water dis-
charge nozzle and secure using a hose clip.
Lay the hose as per the instructions above.
5.4 Electrical connection
5.4.1 Notes on electrical installation
When carrying out the electrical installation, it is impor-
tant to observe all valid national and regional regula-
tions as well as the provisions of the responsible
power supply company.
Electrical installation must only be carried out by a
qualified electrician who is responsible for compliance
with the existing standards and regulations.
The mains infeed and the signal cable must be of a
shielded design. The shielding can be connected to
the earth lug provided in the connection area of the
mains connector.
All cables routed into the wiring compartment have to
be insulated for the maximum voltage of the power
supply.
Connection data
The connected voltage and frequency must corre-
spond to the ranges stated on the rating plate. The
units support multiple voltages.
The cooling unit must be connected to the mains via
an all-pole disconnect to overvoltage category III (IEC
61058-1).
No additional temperature control may be connected
upstream of the unit at the supply end
Install a pre-fuse to match the supply voltage used and
the specific electrical output of the cooling unit. The
rated values may be taken from section 10 "Technical
specifications" below.
Low-noise potential equalisation must be guaranteed
with the mains connection.
In order to prevent EMC interference, the unit should
be incorporated into the existing potential equalisation
system with a larger cable cross-section (10 mm²).
Overvoltage protection and supply line load
The unit does not have its own overvoltage protection.
Measures must be taken at the supply end by the
switchgear manufacturer or operator to ensure effec-
tive protection against lightning and overvoltage. The
limits specified in standard UL/IEC/EN 60335-2-40
must be observed.
The units are classified as overvoltage category III. The
mains voltage must not deviate by more than the tol-
erance specified in section 10 "Technical specifica-
tions".
The discharge current may exceed 3.5 mA.
The units are high-voltage tested ex works. An addi-
tional high voltage test must only be carried out with a
DC voltage supply source (1500 VDC max.).
Three-phase devices
There is no need to observe a counterclockwise or
clockwise phase rotation when making the electrical
connection for inverter devices in the three-phase ver-
sion. The electronics incorporated into the devices au-
tomatically create the required phase rotation.
In three-phase devices, the absence of a phase is de-
tected, and the device is switched off.
Outgoing equipment is monitored by the inverter, and
deactivated in the event of a malfunction in the elec-
tricity supply.
Door limit switch
Each door limit switch can only be assigned to one
cooling unit.
Several door limit switches may be operated in parallel
with one cooling unit.
The minimum cross-section for the connection cable
is 0.3 mm² for a cable length of 2 m.
The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
The maximum admissible line length is 10 m.
The door limit switch only supports a floating connec-
tion; no external voltages.
The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch is
provided by the internal power pack: Current approx.
5mA DC.
Connect the door limit switch to terminals 5 and 6 of
the signal connector.