User manual

Rittal enclosure cooling unit 21
5 Installation
EN
Fig. 34: Connections at rear
Key
1 Connection for communication module (X3)
2 Connection for signal connector (X2)
3 Connection for mains connector (X1)
4 Bolt (here with fitted earth clamp)
Potential equalisation
If the unit is to be integrated into the customer's existing
potential equalisation system for EMC reasons, a con-
ductor with a larger nominal cross-section of at least
10 mm² can be connected to the potential equalisation
connection point (attachment points) on wall-mounted
cooling units. The connection point is labelled with the
required switch symbol.
Fig. 35: Connection point for potential equalisation
Key
1 Connection point
Attach the potential equalisation to the unit's connec-
tion point using the screw, washer and contact wash-
er.
Fig. 36: Potential equalisation arrangement
Key
1 Ring terminal with PE conductor
2 Contact washer
3Washer
4 Screw
5.4.2 Install the power supply
Remove the mains connector from the dispatch bag
and connect to the mains as shown on the connection
diagram (fig. 37 or fig. 38).
Fig. 37: Circuit diagram SK 3186930 and SK 3187930
Note:
According to the standard, the PE conductor
in the mains connection cable is not classed
as an equipotential bonding conductor.
Note:
The mains supply must be of a shielded
design with preferred EMC types in order
to achieve the values required by the
standard.
The earth clamp may be used to contact
the cable shielding with the enclosure in-
side the connection box (fig. 34, item 4).