5 Installation
EN
22 Rittal enclosure cooling unit
Fig. 38: Circuit diagram SK 3188940 and SK 3189940
There is also a cover for the connection box included in
the dispatch bag.
Insert the EMC cable gland included with the supply
into the openings in the cover to ensure adequate
strain relief for the connection cable.
Close the connection box with the cover.
Cover any unused openings in the cover with sealing
bungs.
When connecting the cooling unit in accordance with
NFPA 70 (NEC):
Use a conduit fitting instead of the cable gland.
Use copper conductors only to connect the supply ca-
ble to the mains connector.
5.4.3 Connect the alarm relays
System messages from the cooling unit may be output
to an external signal source via two floating relay out-
puts.
Connect a suitable connection cable to the connec-
tion terminals 1 (Alarm K1) and/or 3 (Alarm K2) of the
signal connector (X2).
Configure the alarm relays you wish to use to output
error messages (see section 7.4.2 "Alarm relays").
5.4.4 Interfaces
The cooling unit has the following interfaces for commu-
nicating with external systems:
Micro-USB interface on the front
RS 485 interface on the rear
–NFC interface
Micro-USB interface
A micro-USB interface is located on the front, to the right
of the display. A tablet or laptop may be connected here
for easy configuration of the unit.
Connect a tablet or laptop with installed RiDiag soft-
ware to the micro-USB interface.
No other USB devices will be detected on this connec-
tion.
RS 485 interface
An RS 485 interface is located on the rear of the connec-
tion box. The communication module with which you
can connect the cooling unit to a monitoring system
(Rittal CMC), may be connected here.
Connect the communication module (available as an
accessory) to the RS 485 interface.
NFC interface
The cooling unit may be accessed with a smartphone
app via the integral NFC interface. Access is only possi-
ble with the app supplied by Rittal.
Note:
The factory setting of the relay outputs in their
de-energised state is NO (Normally Open).
AC
cos φ = 1
I max. = 2 A
U max. = 250 V
Tab. 2: Contact data
Note:
A direct connection to the cooling unit via the
RS 485 interface is not possible.