30 Rittal enclosure cooling unit
Internal fan Alarm 1 1 The fan in the internal circuit of your cooling unit is blocked. Please check
if you can see a blockage and remove it. If no blockage is visible, please
replace the fan in the internal circuit. The required spare part may be or-
dered directly from Rittal using the Blue e+ app. Please use the contact
form "Generate service order".
Internal fan Alarm 2 1 The fan in the internal circuit of your cooling unit is defective. Please re-
place the fan in the internal circuit. The required spare part may be or-
dered directly from Rittal using the Blue e+ app. Please use the contact
form "Generate malfunction report".
External fan Alarm 1 1 The fan in the external circuit of your cooling unit is blocked. Please check
if you can see a blockage and remove it. If no blockage is visible, please
replace the fan in the external circuit. The required spare part may be or-
dered directly from Rittal using the Blue e+ app. Please use the contact
form "Generate service order".
External fan Alarm 2 1 The fan in the external circuit of your cooling unit is defective. Please re-
place the fan in the external circuit. The required spare part may be or-
dered directly from Rittal using the Blue e+ app. Please use the contact
form "Prepare malfunction report".
Inverter cooler The cooling body of the inverter in your cooling unit is dirty. Please re-
move the filter grille and the cover at the front and clean the cooling body,
e.g. using compressed air.
The error message will terminate automatically approximately 30 sec-
onds after it has been resolved.
Compressor defective 2 The compressor in your cooling unit is reporting a malfunction. Please
contact the Rittal Service team immediately.
Sensor xx defective 1 Sensor xx in your cooling unit is reporting a sensor failure. Please contact
the Rittal Service team.
Ext. sensor missing 1 The external sensor is not connected or has a malfunction. Please check
the connection or select another control mode.
Check voltage 1 You are operating your cooling unit outside of the admissible voltage
ranges. Please check the power supply to the cooling unit and observe
the specifications on the rating plate. With a three-phase infeed, please
also check that all three phases are correctly connected.
Electronic fault 2 The electronics in your cooling unit are reporting an electronic fault.
Please contact the Rittal Service team.
Check parameters Due to an error, the cooling unit has been reset to the factory defaults.
Please check the current messages or contact your Rittal Service team.
Inverter fault 2 The inverter in your cooling unit is reporting a malfunction. Please contact
the Rittal Service team.
System message Alarm relay output
(factory setting)
Troubleshooting measures/solutions
Tab. 15: Error messages