8 Inspection and maintenance
EN
34 Rittal enclosure cooling unit
Fig. 47: Remove the infill panel
Key
1 Mounting clips
2Cover
3 Infill panel
On the rear of the display, disconnect both of the con-
nectors (PE conductor and connection) and remove
the infill panel completely from the cooling unit.
Fig. 48: Connection point on rear of cooling unit
Key
1 Connection point
Place the infill panel somewhere safe.
Carefully push the connector including connection ca-
ble inwards through the cable gland in the cover.
Fig. 49: Cable gland in cover
Key
1Cover
2 Cable gland
Loosen the six fixing clamps used to connect the cool-
ing unit and enclosure door or side panel.
You may wish to use a screwdriver to press the stays
back and remove the fixing clamps.
Fig. 50: Loosen the fixing clamps
Key
1 Enclosure door or side panel
2 Opening for screwdriver in cooling unit
3Stays
4 Fixing clamps
Allow the unit to cool down for at least ten minutes be-
fore removing the cover.
This should allow hot surfaces inside the unit to cool
down sufficiently.
Loosen the four threaded bolts in the corners of the
cover which connect the cover to the chassis.
Carefully pull the cover forwards (approx. 5 cm) from
the chassis.
The PE conductor connection between the cover and
the chassis is located o the right-hand side, around
half-way up.
Caution!
The cooling unit will only be stable as
long as the cover and chassis are con-
nected. For this reason, be sure to brace
the chassis, in particular, to stop it falling
over before removing the cover.
Caution!
After removing the cover, there is a risk
of burn injuries from hot component sur-
faces inside the unit.