Data Sheet

Air/water heat exchangers
20 Rittal Hygienic DesignFurther technical information available on the Internet.
Accessories for climate control Cat. 35, page 454Chillers Cat. 35, page 446Therm software Cat. 35, page 474
Air/water heat exchanger for
hygienically sensitive production
zones in the food and consuma-
bles industry – the optimum addi-
tion to the Rittal Hygienic Design
range. The cleaning-friendly
design reduces the risk of con-
tamination and ensures food
safety.
Benefits:
Easy-to-clean, hygienic design
A roof tilt of 30° prevents
objects from being deposited
on it, and allows liquids to run
off quickly.
All-round external, replaceable
silicone seal prevents the accu-
mulation of dirt between the
enclosure and the air/water
heat exchanger.
Material:
Enclosure: Stainless steel
1.4301 (AISI 304)
Surface finish:
Enclosure: Brushed, grain 400,
peak-to-valley height < 0.8 μm
Protection category IP to
IEC60529:
–IP 56/59
Protection category NEMA:
NEMA 4X
Cooling medium:
Water (see Internet for specifi-
cations)
Supply includes:
Fully wired ready for connec-
tion (plug-in terminal strip)
Drilling template
Sealing and assembly parts
Note:
To achieve a protection cate-
gory of IP 66/69 to IEC 60 529,
the ingress of leakage air
through the condensate dis-
charge opening must be com-
pletely prevented.
Output class600 – 1300 W, wall-mounted HD
Model No. Packs of 3214.700 3215.700
Cat. 35,
page
Temperature control Thermostat-controlled magnetic valve
Total cooling output L35 W10, 200 l/h kW 0.6 1
Total cooling output L35 W10, 400 l/h kW 0.65 1.2
Power consumption P
el
50/60 Hz W 36 / 37 83 / 85
Rated operating voltage V, ~, Hz 230, 1~, 50/60 230, 1~, 50/60
Width mm 220 215
Height mm 526 982
Depth mm 100 100
Rated current max. A 0.16 / 0.14 0.38 / 0.47
Pre-fuse A 2 4
Operating temperature range +1°C...+70°C +1°C...+70°C
Setting range +20°C...+60°C +20°C...+60°C
Water inlet temperature +1°C...+30°C +1°C...+30°C
Water connection G ⅜" external thread
Permissible operating pressure (p. max.) bar 1 - 10 1 - 10
Air throughput of fans (unimpeded air flow), Internal circuit 50/60 Hz m³/h 280 / 310 680 / 735
Weight kg 6.0 14.0
Accessories
Toroidal transformer see page see page 471
Cooling medium (ready-mixed) see page see page 465