Operating instructions
Table Of Contents
- Doku_Standard_Wasser-RK_GB_V09.pdf
- General description
- Important safety measures
- Transport and handling
- Installation
- Electrical connection
- Start-up
- Hydrological data
- Maintenance
- Shutting down / disposing the cooling system
- General fault analysis
- Evaporator pressure
- Compressor is continuously being switched on and off
- No medium circulation
- Appendix
- Datenblatt_060535.pdf
- PID.pdf
- Schaltplan_englisch.pdf
- MPRA-SMK-A-0-Englisch.pdf
- BA_PMA-KS40-1_41-1_42-1_englisch.pdf
- Contents
- 1 Mounting 5
- 2 Electrical connections 6
- 3 Operation 10
- 4 Configuration level 21
- 4.1 Configuration survey 21
- 4.2 Configuration 22
- 4.3 Set-point processing 29
- 4.4 Configuration examples 30
- 4.4.1 On-Off controller / Signaller (inverse) 30
- 4.4.2 2-point controller (inverse) 31
- 4.4.3 3-point controller (relay & relay) 32
- 4.4.4 3-point stepping controller (relay & relay) 33
- 4.4.5 Continuous controller (inverse) 34
- 4.4.6 D - Y - Off controller / 2-point controller with pre-contact 35
- 4.4.7 KS4x-1 with measured value output 36
- 5 Parameter setting level 37
- 6 Calibration level 41
- 7 Programmer 44
- 8 Timer 46
- 9 BlueControl 49
- 10 Versions 50
- 11 Technical data 51
- 12 Safety hints 55
- Index
- Contents
- Parameterliste PMA_english.pdf
- BA_Strömungswächter_SI1000_englisch.pdf
- BA-IFM_Drucksensor PN7009_englisch.pdf
- Endress-Hauser-Display BA188Ra3_englisch.pdf
- Endress-Hauser-Messsonde_BA_englisch.pdf
- BA_FEC12_englisch.pdf
Adjustable parameters
22
Technical informations / Functioning / Parameters
Switch-on point 1 / 2:
Upper limit value at which the output changes its switching
status.
Setting range → page 38 / 39.
SP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching sta-
tus.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is auto-
matically reduced (rPx is set to the minimum setting value).
Setting range → page 38 / 39.
rP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
Configuration of output 2
4 switching functions and the diagnostic function can be set:
- Hno = hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
-
dESI = Output 2 is used as a diagnostic output
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button
briefly.
If the submenu is protected with an access code,"Cod1" flashes
in the display.
- Press the "Set" button and hold it pressed until the valid code
no. is shown.
- Then briefly press the "Mode/Enter" button.
Delivery by ifm electronic: no access restriction.