Operating instructions

12 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
4.5 Notes on electrical installation
When performing the electrical installation, it is im-
portant to observe all valid national and regional reg-
ulations as well as the provisions of the responsible
power supply company. Electrical installation must
only be carried out by a qualified electrician who is re-
sponsible for compliance with the existing standards
and regulations.
4.5.1 Connection data
The connected voltage and frequency must
correspond to the values stated on the rating plate.
The cooling unit must be connected to the mains
via an all-pin isolating device, which ensures at
least 3 mm contact opening when switched off.
No additional temperature control may be connec-
ted upstream of the unit at the supply end.
Install the pre-fuse specified on the rating plate
to protect the cable and equipment from short-
circuits.
The mains connection must ensure low-noise
potential equalisation.
4.5.2 Overvoltage protection and supply line
load
The unit does not have its own overvoltage pro-
tection. Measures must be taken by the operator at
the supply end to ensure effective lightning and
overvoltage protection. The mains voltage must not
exceed a tolerance of ±10%.
In accordance with IEC 61 000-3-11, the unit is
intended solely for use at sites with a continuous
current-carrying capacity (incoming mains power
supply) of more than 100 A per phase and with
a supply voltage of 400/230 V. If necessary, the
power supply company must be consulted to
ensure that the continuous current-carrying capa-
city at the point of connection to the public grid is
sufficient for connection of such a unit.
The fans and compressors in single- and three-
phase units are intrinsically safe (thermal winding
protection). The same also applies to the transfor-
mer versions of types SK 3304.110, SK 3304.510,
SK 3305.110, SK 3305.510, SK 3328.110,
SK 3328.510, SK 3329.110 and SK 3329.510
and to special-voltage units which are likewise
equipped with a transformer.
Install the slow pre-fuse specified on the rating
plate (miniature circuit-breaker with “K” charac-
teristic, circuit-breaker for plant or transformer
protection) to protect the cable and equipment from
short-circuits. Select a suitable circuit-breaker in
accordance with the information specified on the
rating plate: Set it to the minimum specified value.
This will achieve the best short-circuit protection for
cables and equipment.
Example: Specified setting range 6.3 – 10 A;
set to 6.3 A.
4.5.3 Three-phase devices
The three-phase version of models SK 3304.xxx,
SK 3305.xxx, SK 3328.xxx, SK 3329.xxx and
SK 3332.xxx must be connected to a TN network
with star earthing via a circuit-breaker for plant
protection (current setting as per the rating plate).
Three-phase units with special voltages must be
protected with a circuit-breaker for transformer
protection (category AC-3) as per the rating plate.
Units designed for three phase 400/460 V feature
additional monitoring of the rotary field or the
absence of a phase. If the rotary field is incorrect or
a phase is absent, the unit will not run.
4.5.4 Door limit switch
Each door limit switch must only be assigned to one
cooling unit.
Several door limit switches may be connected in
parallel and operated on one cooling unit.
The minimum cross-section for the connection
cable is 0.3 mm
2
for a cable length of 2 m.
The line resistance to the door limit switch must not
exceed a maximum of 50
.
The door limit switch only supports a floating
connection; no external voltages.
The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch
is
provided by the internal power pack: Current
approx. 30 mA DC.
Connect the door limit switch to terminals 1 and 2 of
the connector.
4.5.5 Notes on the flicker standard
The flicker limits specified in standard EN 61 000-3-3
or -3-11 are adhered to, provided the supply im-
pedance is less than approx. 1.5
.
Where necessary, the unit operator should measure
the connected impedance or consult the responsible
power supply company. If there is no way of influenc-
ing the supply impedance and sensitive installed
components (e.g. BUS) are subjected to interference,
a line reactor or starting-current limiting device should
be connected upstream of the cooling unit to restrict
the startup current of the cooling unit.
4.5.6 Potential equalisation
RITTAL recommends connecting a conductor with a
nominal cross-section of at least 6 mm
2
to the poten-
tial equalisation connection point on wall-mounted
cooling units, and incorporating it into the existing po-
tential equalisation system.
According to the standard, the PE conductor in the
mains connection cable is not classified as an equi-
potential bonding conductor.