Operating instructions

6 Operation
RITTAL cooling unit assembly and operating instructions 23
EN
6 Operation
You can operate the cooling unit using the controller
on the front of the device (Fig. 1, no. 11, page 5).
Depending on the model, the unit is equipped with
a Basic or Comfort controller.
6.1 Control using the Basic controller
For unit types SK xxxx.100/.110/.140 and
SK xxxx.200/.210/.240/.300/.310.
Fig. 36: Basic controller
Legend
1 Controller trim panel
2 Temperature setting
3 LED green (“line”)
4 LED red (“alarm”)
5 Reset button
6.1.1 Properties
Three voltage variants are supported:
115 V
230 V
400/460 V, 3-phase
Supports multiple voltages without rewiring
Integral start-up delay and door limit switch
function
Protective function to prevent icing
Monitoring of all motors (compressor,
condenser fan, evaporator fan)
Phase monitoring for three-phase units
Visualisation of the operating status via LED
display:
Voltage on, unit operational
Door open (only if door limit switch installed)
Warning of overtemperature
High-pressure-operated switch has switched
Switching hysteresis: 5 K
Floating system message contact in case
of overtemperature
Temperature setting
(setting range 30 – 55°C) via potentiometer
Test function
The cooling unit operates automatically i.e. after
switching on the power supply, the evaporator fan
(see Fig. 2, page 5) will run continuously and perma-
nently circulate the internal enclosure air. The built-in
Basic controller ensures automatic normal shut-
down operation of the cooling unit by the value of the
fixed preset switching difference of 5 K.