Operating instructions

42 RITTAL cooling unit assembly and operating instructions
9 Technical specifications
EN
Unit
Model No. SK
Basic controller,
RAL 7035
3302.100 3302.110 3302.300 3302.310 3303.100 3303.110 3304.100 3304.110 3304.700
Comfort controller,
RAL 7035
––––3303.500 3303.510 3304.500 3304.510 3304.800
Basic controller,
stainless steel cover
3302.200 3302.210 3303.200 3303.210 3304.200 3304.210
Comfort controller,
stainless steel cover
––––3303.600 3303.610 3304.600 3304.610
Rated voltage
V
Hz
230, 1~,
50/60
115, 1~,
60
230, 1~,
50/60
115, 1~,
60
230, 1~,
50/60
115, 1~,
60
230, 1~,
50/60
115, 1~,
50/60
230, 1~,
50
Rated current A 1.6/1.7 3.3 1.6/1.7 4.0 2.6/2.6 5.7 5.4/5.0 10.6/11.1 3.0
Start-up current A 3.0/3.4 8.0 4.3/5.3 12.0 5.1/6.4 11.5 12.0/14.0 26.0/28.0 12.0
Pre-fuse T A 10.0 10.0 10.0 10.0 10.0 10.0 10.0
11.0 – 16.0
10.0
Motor circuit-breaker ––––––––
Transformer circuit-breaker –––––––
Miniature circuit-breaker/fuse       
Useful cooling output
Q
k
L 35 L 35
to DIN 3168 L 35 L 50
W
W
300/320
150/170
300
150
300/320
150/160
300
150
500/610
280/350
500
280
1000/1060
790/840
1000/1060
790/840
1000
900
Power consumption P
el
L 35 L 35
to DIN 3168 L 35 L 50
W
W
245/255
255/275
290
340
285/300
320/340
290
340
360/380
420/390
470
500
825/775
875/835
850/800
900/875
520
580
Refrigeration factor ε = Q
k
/P
el
1.2 1.2 1.1 1.1 1.4 1.4 1.2 1.2 1.9
Refrigerant
– Type
– Filling
g
R134a
100
R134a
95
R134a
170
R134a
170
R134a
325
R134a
325
R134a
500
Admissible pressure bar 25 25 25 25 28 28 25 25 28
Temperature setting range
1)
°C +20 to +55
+20 to +45
Noise level dB (A) < 61 < 61 < 61 < 61 < 61 < 61 < 61 < 64 < 64
Protection category to EN 60 529
– Internal circuit
– External circuit
IP 54
IP 34
Dimensions (W x H x D) mm 280 x 550 x 140 525 x 340 x 153
280 x 550 x
200
400 x 950 x 260
Weight kg 13 13 13 17 17 17 39 44 40
1)
Basic controller +30°C to +55°C
.
.