Operating instructions

44 RITTAL cooling unit assembly and operating instructions
9 Technical specifications
EN
Unit
Model No. SK
Basic controller, RAL 7035 3329.110 3329.140 3332.140 3361.100 3361.110 3361.140
Comfort controller, RAL 7035 3329.510 3329.540 3332.540 3361.500 3361.510 3361.540
Basic controller,
stainless steel cover
3329.210 3329.240 3332.240 3361.200 3361.210 3361.240
Comfort controller,
stainless steel cover
3329.610 3329.640 3332.640 3361.600 3361.610 3361.640
Rated voltage V, Hz
115, 1~,
50/60
400, 3~, 50/
460, 3~, 60
400, 3~, 50/
460, 3~, 60
230, 1~,
50/60
115, 1~,
60
400, 2~,
50/60
Rated current A 17.0/22.0 3.7/3.8 4.2/4.2 2.3/2.4 5.3 1.2/1.4
Start-up current A 44.0/42.0 6.8/7.6 9.2/11.0 5.6/5.6 12.0 3.1/3.3
Pre-fuse T A 18.0 – 25.0 6.3 – 10.0 6.3 – 10.0 10.0 10.0 6.3 – 10.0
Motor circuit-breaker –––
Transformer circuit-breaker –––
Miniature circuit-breaker/fuse
Useful cooling output Q
k
L 35 L 35
to DIN 3168 L 35 L 50
W
W
2500/2750
1600/1750
2500/2700
1900/1950
4000/4400
3070/3570
750/780
510/540
750
500
750/780
510/540
Power consumption P
el
L 35 L 35
to DIN 3168 L 35 L 50
W
W
1500/1725
1675/2065
1425/1625
1675/1975
1850/2250
2120/2590
480/550
530/640
570
670
480/550
530/640
Refrigeration factor ε = Q
k
/P
el
1.7 1.8 2.1 1.5 1.5 1.5
Refrigerant
– Type
– Filling
g
R134a
950
R134a
950
R134a
3000
R134a
280
R134a
260
R134a
280
Admissible pressure bar 28 28 28 28 28 28
Temperature setting range
1)
°C +20 to +55 +20 to +52 +20 to +55
Noise level dB (A) < 64 < 64 < 64 < 64 < 64 < 64
Protection category to EN 60 529
– Internal circuit
– External circuit
IP 54
IP 34
Dimensions (W x H x D) mm 400 x 1580 x 290
500 x 1580 x 340
280 x 550 x 280
Weight kg 76 70 91 22 22 22
Unit
Model No. SK
Basic controller, RAL 7035 3366.100 3366.110 3366.140 3377.100 3377.110 3377.140
Comfort controller, RAL 7035 3366.500 3366.510 3366.540 3377.500 3377.510 3377.540
Basic controller,
stainless steel cover
3366.200 3366.210 3366.240 3377.200 3377.210 3377.240
Comfort controller,
stainless steel cover
3366.600 3366.610 3366.640 3377.600 3377.610 3377.640
Rated voltage V, Hz
230, 1~,
50/60
115, 1~,
50/60
400, 3~, 50/
460, 3~, 60
230, 1~,
50/60
115, 1~,
50/60
400, 3~, 50/
460, 3~, 60
Rated current A 7.1/7.3 14.3/14.7 3.0/3.1 7.1/7.3 14.3/14.7 3.3/3.4
Start-up current A 22.0/24.0 43.0/47.0 8.0/8.8 22.0/24.0 43.0/47.0 8.0/8.8
Pre-fuse T A 10.0 14.0 – 20.0 6.3 – 10.0 10.0 14.0 – 20.0 6.3 – 10.0
Motor circuit-breaker ––
Transformer circuit-breaker ––
Miniature circuit-breaker/fuse –– ––
Useful cooling output Q
k
L 35 L 35
to DIN 3168 L 35 L 50
W
W
1500/1500
1050/1100
1500/1500
1050/1100
1500/1500
980/1080
1500/1500
1050/1100
1500/1500
1050/1100
1500/1500
980/1080
Power consumption P
el
L 35 L 35
to DIN 3168 L 35 L 50
W
W
1045/1175
1220/1335
1075/1200
1265/1375
1090/1240
1260/1430
1045/1175
1220/1335
1075/1200
1265/1375
1090/1240
1260/1430
Refrigeration factor ε = Q
k
/P
el
1.4 1.4 1.3 1.4 1.4 1.3
Refrigerant
– Type
– Filling
g
R134a
700
R134a
700
R134a
700
R134a
700
R134a
700
R134a
700
Admissible pressure bar 28 28 28 28 28 28
Temperature setting range
1)
°C +20 to +55
Noise level dB (A) < 64 < 64 < 64 < 64 < 64 < 64
Protection category to EN 60 529
– Internal circuit
– External circuit
IP 54
IP 34
Dimensions (W x H x D) mm 450 x 1590 x 195 450 x 1590 x 165
Weight kg 45 50 46 45 50 46
1)
Basic controller +30°C to +55°C
.
.
.
.