Instruction manual
5. SETTING 
IMR01Y06-E6  17 
5.2 Communication Speed Setting 
The rotary switch at the left side of the mainframe sets the communication speed of the CC-Link. 
For this setting, use a small slotted screwdriver. 
When set to any value out of the setting range, the COM-JC becomes the FAIL state. 
Left side view 
Communication speed 
setting switch 
Setting range: 0 to 4 
Factory set value: 0 (156 kbps) 
z Communication speed and maximum transmitter distance   
(Use the CC-Link dedicated cable Ver. 1.10) 
Communication 
speed setting 
Communication 
speed 
Maximum transmitter distance 
(maximum length of network) 
0 156 kbps  1200 m 
1 625 kbps  900 m 
2 2.5 Mbps  400 m 
3 5 Mbps  160 m 
4 10 Mbps  100 m 