Instruction manual
7. COMMUNICATION DATA LIST 
IMR01Y06-E6 
66 
Continued from the previous page. 
Extension 
number 
Communication item 
Attri-
bute
Data range 
Factory 
set value
152 
Heater break determination 
point 2 
R/W
0.0 to 100.0 % of HBA2 set value 
(0.0: Heater break determination is invalid) 
If there is no Current transformer 2 (CT2) or 
CT2 is assigned to “0: None,” set to RO (Read 
only data). 
If Heater break alarm 2 (HBA2) corresponds 
to “0: Type A,” set to RO (Read only data). 
30.0 
153 
Heater melting 
determination point 2 
R/W
0.0 to 100.0 % of HBA2 set value 
(0.0: Heater melting determination is invalid) 
If there is no Current transformer 2 (CT2) or 
CT2 is assigned to “0: None,” set to RO (Read 
only data). 
If Heater break alarm 2 (HBA2) corresponds 
to “0: Type A,” set to RO (Read only data). 
30.0 
154 Unused 
⎯ 
⎯
⎯
y 
y 
y 
159 
160 
Display unit 
R/W
0:  °C 
1:  °F 
Use to select the temperature unit for 
Thermocouple (TC) and RTD inputs. 
Based on 
model code.
When not 
specifying: 0
161 
Input scale high 
R/W
TC/RTD inputs: 
Input scale low to Maximum value of the 
selected input range 
Voltage (V)/Current (I) inputs: 
−19999 to +19999 
Varies with the setting of the Decimal point 
position selection. 
TC/RTD: 
Maximum 
value of the 
selected 
input range
V/I: 100.0
162 
Input scale low 
R/W
TC/RTD inputs: 
Minimum value of the selected input range 
to Input scale high 
Voltage (V)/Current (I) inputs: 
−19999 to +19999 
Varies with the setting of the Decimal point 
position selection. 
TC/RTD: 
Minimum 
value of the 
selected 
input range
V/I: 0.0 
163 
Input error determination 
point (high) 
R/W
Input scale low 
−
 (5 % of input span) to 
Input scale high + (5 % of input span) 
Varies with the setting of the Decimal point 
position selection. 
TC/RTD: 
Input scale 
high + (5 % 
of input span)
V/I: 105.0
164 
Input error determination 
point (low) 
R/W
TC/RTD: 
Input scale 
low − (5 % 
of input span)
V/I: −5.0 
Continued on the next page. 