2 VDC Beacon 200 Operator’s Manual Part Number: 71-0293RK Revision: P1 Released: 10/4/13 www.rkiinstruments.
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
Table of Contents Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 About the 12 VDC Beacon 200 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications . . . . . . . .
Chapter 6: Input Setup Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Setting up a New Channel or Changing an Existing Channel. . . . . . . . . . . . . . . 33 Chapter 7: Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1: Introduction Overview This chapter briefly describes the 12 VDC Beacon 200. This chapter also describes the 12 VDC Beacon 200 Operator’s Manual (this document). Table 1 at the end of this chapter lists the specifications for the 12 VDC Beacon 200. About the 12 VDC Beacon 200 The 12 VDC Beacon 200 is a fixed-mounted, continuous-monitoring gas detection instrument. This gas monitor is capable of detecting gas at two locations.
About this Manual The 12 VDC Beacon 200 Gas Monitor Operator’s Manual uses the following conventions for notes, cautions, and warnings. NOTE: Describes additional or critical information. CAUTION: Describes potential damage to equipment. WARNING: Describes potential danger that can result in injury or death.
Specifications Table 1 lists specifications for the 12 VDC Beacon 200. Table 1: 12 VDC Beacon 200 Specifications Description Specification Input Power 10.8 - 14.5 VDC, 1.2A VDC Construction (housing) Fiberglass/polyester with lexan window (NEMA 4X) Controller Dimensions 10.5 in. H x 8.5 in. W x 6.25 in. D (267 mm H x 216 mm W x 158 mm D) Weight 8 lbs. Environmental Conditions • • -20°C to 50°C (-4°F to 122°F) max.
Chapter 2: Description Overview This chapter describes external and internal components of the 12 VDC Beacon 200.
External Description This section describes the housing and all external components of the 12 VDC Beacon 200. For the purposes of this description, the housing door is considered the front of the monitor. Housing The 12 VDC Beacon 200’s fiberglass housing is weather- and corrosionresistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side.
Internal Description This section describes the internal components of the 12 VDC Beacon 200. Display Printed Circuit Board (PCB) The display PCB is mounted to the power supply mounting plate which is in turn mounted to the main PCB. The power supply mounting plate and main PCB are described below. The display PCB includes the display, the status lights, and the program buttons.
Status Lights The 12 VDC Beacon 200 includes four status lights that indicate the current status of the monitor. The status lights are to the left and right of the display (see Figure 2). • Pilot Light. The pilot light is on when the 12 VDC Beacon 200 is receiving incoming power. • Fail Light. The fail light turns on when the 12 VDC Beacon 200 is experiencing a fail condition. A fail condition can be caused by a failure within the 12 VDC Beacon 200 or detector head(s) wired to the 12 VDC Beacon 200.
Main PCB The main PCB is mounted inside the housing. The power supply mounting plate is mounted to the main PCB with four standoffs and the display PCB is mounted to the power supply mounting plate with four standoffs. The main PCB includes the terminal strips, relays, fuses, and power switch. Terminal Strips The 12 VDC Beacon 200 includes four terminal strips for external wiring connections. See “Wiring the 12 VDC Beacon 200” on page 13 for detailed wiring procedures.
• DC In Terminal Strip. The DC in terminal strip is a 3-point terminal strip located above the controller terminal strip (see Figure 1). It facilitates wiring from a 12 VDC power source. Table 4 lists the function of each terminal.
NOTE: The alarm 2 channel relays may be set to operate as individual channel fail relays. See “Configure Channel Settings Menu” on page 30 for instructions. • Common relays. The three common relays, alarm 1, alarm 2, and fail, are to the left of the controller terminal strip (see Figure 1). These relays are common for both channels. For example, the alarm 1 common relay energizes if either channel 1 or channel 2 recognizes an alarm 1 condition.
Chapter 3: Installation and Start Up Overview This chapter describes procedures to mount the 12 VDC Beacon 200, make wiring connections to the monitor, and start up the monitor. WARNING: Perform all installation and start-up procedures in a “fresh air” environment (known to be free of combustible gas, toxic gas, and of normal oxygen content). The 12 VDC Beacon 200 is not in operation as a gas monitoring system until the start-up procedure is complete.
.41 8.50 Mounting Feet, 4X 6.00 Ø .31 x .50 slot, 4X FAIL ALARM 2 6.45 10.50 ALARM 1 PILOT 10.94 BEACON 200 GAS MONITOR RESET Reset Switch Buzzer 3/4 Conduit Hubs (4X) Figure 4. 12 VDC Beacon 200 Outline and Mounting Dimensions 1. Select the mounting site.
Wiring the 12 VDC Beacon 200 This section describes procedures to connect the 12 VDC power source, external alarm(s), a recorder, and detector head(s). See Figure 5 for a general wiring diagram of all external wiring to the 12 VDC Beacon 200. DC In Terminal Strip Wiring + 12 V DC Typical Detector/Transmitter Terminal Strip Wiring Controller Terminal Strip Wiring Only one detector or transmi tter can be wired to Ch1 or Ch2 at a time. See detector head wiring diagram for specific wi ring.
The power converter, reset switch, and alarm buzzer are all factory wired. MAIN PCB P1 Power Converter TB1 P2 + 12 V DC NOT USED + CH1 OUT + CH2 OUT RESET SWITCH BUZZER RESET RESET BUZ BUZ + Figure 6. 12 VDC Beacon 200 Factory Wiring Diagram WARNING: Make all connections to the 12 VDC Beacon 200 before you connect the DC power source. Before you make any wiring adjustments, always verify that all power sources are not live.
3. Install an appropriately rated cable bushing or conduit in an unused conduit hub on the bottom of the 12 VDC Beacon 200 housing. 4. Guide the power wiring through the selected conduit hub on the bottom of the 12 VDC Beacon 200 housing. CAUTION: Do not route the power wiring and detector head wiring through the same conduit hub. The power wiring may disrupt the transmission of the detector signal to the 12 VDC Beacon 200. 5.
5. Connect the leads from the external alarm device and power to the alarm terminals as shown in Figure 8. Beacon 200 Alarm Terminal Strip CH1-A1 NO NC C + (H) External Alarm Device - (N) External Power Source Figure 8. Typical External Alarm Wiring 6. Repeat steps 4 and 5 for additional external alarm devices. Connecting a Recorder Perform the following procedure to connect an analog recording device to the 12 VDC Beacon 200.
5. Connect the wires from the recording device to the recorder output terminals as shown in Figure 9. Recording Device #1, 1Kohm Max Impedance Recording Device #2, 1Kohm Max Impedance + + CH1 OUT + CH2 OUT + Figure 9. Recorder Output Wiring Connecting RKI Detector Heads Perform the following procedure to connect an RKI detector head to the 12 VDC Beacon 200. 1. Turn off or unplug power to the 12 VDC Beacon 200. 2. Open the 12 VDC Beacon 200 housing door and place the power switch in the off position.
Table 5: Wire Size Guidelines for RKI Detector Head Wiring Number of Wires to Controller Max Distance to Controller w/18 Gauge Wire Max Distance to Controller w/ 16 Gauge Wire Max Distance to Controller w/14 Gauge Wire Direct Connect LEL 4 500 ft. 1,000 ft. 2,000 ft. Direct Connect Oxygen 2 500 ft. 1,000 ft. 2,000 ft. Direct Connect H2S 2 500 ft. 1,000 ft. 2,000 ft. Direct Connect CO 2 500 ft. 1,000 ft. 2,000 ft. Direct Connect Cl2 2 500 ft. 1,000 ft. 2,000 ft.
CAUTION: Do not route power and transmitter wiring through the same conduit hub. The power wiring may disrupt the transmission of the transmitter’s signal to the 12 VDC Beacon 200. 3-Wire Connection AMP/PREAMP + S LEL OXYGEN + 2-Wire Connection R W AMP/PREAMP G B + S LEL OXYGEN + R W FB (4-20 mA) - (DC GROUND) FB (4-20 mA) 3-Wire 4-20 ma Transmitter + 24 VDC G B 2-Wire 4-20 ma Transmitter + 24 VDC Figure 10.
Starting Up the 12 VDC Beacon 200 Perform the following procedure to place the 12 VDC Beacon 200 into normal operation. 1. Complete the mounting and wiring procedures described earlier in this chapter. 2. Complete all installation procedures described in the detector head or user supplied 4-20 mA transmitter instruction manual. 3. Verify that all wiring connections are correct and secure and that the 12 VDC Beacon 200’s power switch is in the OFF position. 4. Plug in or turn on the 12 VDC power source. 5.
Chapter 4: Operation Overview This chapter describes the 12 VDC Beacon 200 in normal operation. This chapter also describes the 12 VDC Beacon 200 in alarm 1, alarm 2, and fail conditions and suggests response to these conditions. Normal Operation Normal operation is defined as follows: • The start-up procedure is complete. • The 12 VDC Beacon 200 is not indicating an alarm 1, alarm 2, or fail condition. • The 12 VDC Beacon 200 is not running the Channel Control & Setup or Calibration Programs.
Recorder Output Operation The output at the recorder output terminals is a 4 - 20 mA signal for each active channel that is proportional to the detection range of the channel. A channel that is set as CHANNEL NOT USED or CHANNEL DISABLED in the Channel Control & Setup Program (see “Chapter 5: Channel Control and Setup Program” on page 28) has an output of 0 mA.
Alarm Indications This section describes the 12 VDC Beacon 200 in alarm 1, alarm 2, and fail conditions and suggests response to these conditions. Table 6 below lists the alarm indications for each condition. NOTE: The 12 VDC Beacon 200 includes alarm on and alarm off delay settings for each channel and level of gas alarm. The alarm indications described in this section operate according to the factory set delay settings. See “Configure Channel Settings Menu” on page 30 for all the factory settings.
NOTE: You can select normally energized (NE) or normally de-energized (NDE) channel relay settings in the Channel Control & Setup menu. The following sections describe the default setting for the channel relays which is NDE. Common alarm 1 and alarm 2 relays are factory-set as NDE, and the common fail relay is factory set as NE. The common relays’ NE/NDE settings are not user-adjustable.
NOTE: To silence the buzzer while in an alarm 1 condition, press the reset switch. You cannot de-energize the alarm 1 relays and consequently the strobe/horn until the gas reading falls below the alarm 1 setpoint. Alarm 2 Condition This section describes the audible and visual indications for an alarm 2 condition and suggests response to an alarm 2 condition.
Fail Condition This section describes the audible and visual indications for a fail condition and suggests response to a fail condition. Fail Condition Indications The 12 VDC Beacon 200 senses a fail condition for any of the following: • The detector head wiring to the 12 VDC Beacon 200 is disconnected or incorrectly connected. • The detector head’s detector is disconnected or incorrectly connected. • The display reading is -10% of full scale or lower.
the unit may instead shut off if the input voltage decreases below 10.8 V. Viewing & Resetting Min/Max Readings The Reset switch may be used to view and reset the minimum and maximum gas readings for the active channel(s). 1. While the 12 VDC Beacon 200 is in normal operation, press and hold the Reset switch button for 3 seconds. 2. The display will indicate MIN / MAX Display Press RESET when done viewing . . . for 5 seconds before displaying the minimum and maximum readings for the active channel(s).
Chapter 5: Channel Control and Setup Program Overview The Channel Control & Setup Program allows viewing of and changes to instrument setup parameters. It is accessed using the program buttons. The Channel Control & Setup Program includes three menus as described in Table 7.
Enable/Disable Channel(s) Menu 1. From normal operation, simultaneously press and hold the ESCAPE and ENTER buttons for approximately 5 seconds to enter the Channel Control & Setup Program. Release the buttons when the Control & Setup Program Proceed? [YES] or [NO] message appears on the display screen. 2. Press the UP/YES button to continue. 3. Press the UP/YES or DOWN/NO button until the 1) Enable/Disable Channel(s) message appears on the display screen, then press the ENTER button. 4.
Configure Channel Settings Menu This section describes how to view and change channel parameters for the installed gas channels. 1. Simultaneously press and hold the ESCAPE and ENTER buttons for approximately 5 seconds to enter the Channel Control & Setup Program. Release the buttons when the Control & Setup Program Proceed? [YES] or [NO] message appears on the display screen. 2. Press the UP/YES button to continue. 3.
10. Press the UP/YES button to save the configuration. The screen will then return to the Channel Control & Setup menu. 11. To view or change the Channel 2 settings, scroll to the Configure Channels Menu and repeat steps 4 through 10. 12. To exit the Channel Control & Setup menu, press ESCAPE to return to the screen which asks Control & Setup Program Proceed? [YES] or [NO]. 13. Press the DOWN/NO button to return to normal operation.
Table 9: Channel Setting Parameters (Continued) Parameter (Factory-Set Value) Description ALARM-2 OFF DELAY (0 sec) The amount of time the 12 VDC Beacon 200 delays turning off the alarm 2 circuit once an alarm 2 condition passes. ALARM-2 (activation) (INCREASING) Indicates if the alarm 2 circuit is activated by gas readings INCREASING or DECREASING to the ALARM-2 Level.
Chapter 6: Input Setup Program Overview This chapter describes how to use the Input Setup Program to add a channel or change the channel type of an installed channel on the 12 VDC Beacon 200. The Input Setup Program allows you to define the type of detector head, the units and gas type, and the full scale for that channel. To enter the Input Setup Program, the 12 VDC Beacon 200 must first be off.
describes each type. Table 10: 12 VDC Beacon 200 Detector Head Types Detector Head Type Description 4 - 20 mA Amp [+S(-)] A 4 - 20 mA detector head is connected to the 12 VDC Beacon 200 with 2 or 3 wires, depending on the detector head model, using the AMP/PREAMP +, S, and - terminals on a detector head terminal strip. All calibration adjustments are made at the detector head.
NOTE: See the Beacon 200 Detector Head Specification Sheet for the detector head to determine the correct units and gas type. When the desired units and gas type appears, press the ENTER button to accept the choice. The full scale screen appears. One of the choices is User Will Specify. If the desired units and gas type setting is not in the list, this setting will allow you to enter a 10 character units and gas type setting.
NOTE: Once the 12 VDC Beacon 200 channels are configured correctly, see the detector head operator’s manual(s) for a complete description of detector head installation procedures.
Chapter 7: Maintenance Overview This chapter describes use of the Calibration Program and corrective maintenance procedures for the 12 VDC Beacon 200. It includes a troubleshooting guide for problems you may encounter with the 12 VDC Beacon 200. Procedures to replace components of the 12 VDC Beacon 200 are at the end of this chapter. Calibration Program The Calibration Program is used to calibrate the 12 VDC Beacon 200’s active channel(s).
to guide you through the program. At any point in the calibration program, the ESCAPE key may be used to either return to the previous screen or abort a process. ESCAPE Normal Operation Calibration Program Enter ENTER/ESCAPE ENTER Calibration Timeout Selection Calibrate Channel 1 Y/N? Span Channel 1 Y/N? Calibrate Channel 2 Y/N? (If Installed) Air Adjust Channel 1 Air Adjust Channel 2 (If Installed) Span Channel 2 Y/N? (If Installed) Select Cal. Gas Concentration for Channel 1 Select Cal.
ESCAPE Calibration Program Enter ENTER/ESCAPE Normal Operation Calibrate Channel 2 Y/N? (If Installed) ENTER Calibrate at Detector Head(s) Calibration Timeout Selection Calibrate Channel 1 Y/N? Press Enter When Done Figure 12.
Normal Operation ESCAPE Calibration Program Enter ENTER/ESCAPE ENTER Calibration Timeout Selection Calibrate Channel 1 Y/N? No Calibrate Channel 2 Y/N? Yes Transmitter No Yes Direct Connect Transmitter Direct Connect Calibrate Channel 1 at Detector Head Air Adjust Channel 1 Calibrate Channel 2 at Detector Head Air Adjust Channel 2 Press Enter When Done Select Cal. Gas Concentration for Channel 1 Press Enter When Done Select Cal. Gas Concentration for Channel 2 Apply Gas to Ch.
Entering the Calibration Program 1. Assemble the calibration kit(s). See the instruction manual for each detector head for procedures specific to that detector head. 2. Simultaneously press and hold the ENTER and UP/YES buttons for approximately 5 seconds to enter the Calibration Program. Release the buttons when the CALIBRATION PROGRAM... message displays and asks if you want to continue or return to normal operation.
Calibrating a 4-20 mA detector head 1. The display asks if you want to calibrate channel 1 (in this example a 420 mA detector head). Press the UP/YES button to continue with calibrating channel 1. If you press the DOWN/NO button, the display will skip channel 1 and ask if you want to calibrate channel 2. 2. If you pressed the UP/YES button, since channel 1 is a 4 - 20 mA detector head in this example, the unit will display the following message for a few seconds before continuing: Reminder.
3. If the detector is in a fresh air environment, press the ENTER button. The unit will adjust the zero reading and display the message Fresh Air Adjust Passed for: Channel 2 before continuing. If you suspect the detector area is not a fresh air environment, apply zero air to the detector before pressing the ENTER button. See the detector head instruction manual for instructions to apply zero air to the detector.
9. Press the ENTER button at the 12 VDC Beacon 200 to proceed with the calibration adjustment. If the 12 VDC Beacon 200 is able to successfully make the calibration adjustment, it will display the message Cal Passed for: Channel 2. It will then return to the first calibration program screen which asks if you want to continue or escape from the program. Press ESCAPE to return to normal operation.
CAUTION: Verify that the replacement fuse is the same type and rating as the fuse you are replacing. 6. Install the appropriate replacement fuse in the fuse holder, then place the fuse holder in the socket. 7. Push the fuse holder into the socket, then turn the holder 1/4 turn clockwise to secure it in the socket. 8. Turn on or plug in power to the 12 VDC Beacon 200. 9. Place the 12 VDC Beacon 200’s power switch in the ON position, then verify that the PILOT light is on. 10.
Table 11: Troubleshooting the 12 VDC Beacon 200 (Continued) Condition Frequent or Suspect Alarms Symptom(s) • • Flickering Display • Probable Causes The 12 VDC Beacon 200 alerts you to frequent or suspect alarms. The detector head’s fresh air readings remain on zero (20.9 for oxygen). • The display readings flicker often. • • • • • Buzzer Not Working • • Reset Switch Not Working • • The buzzer does not sound an audible alarm during alarm conditions. The buzzer sounds weak or broken.
Parts List Table 12 lists the part numbers and descriptions for replacement parts and accessories offered for the 12 VDC Beacon 200. Table 12: Parts List, 12 VDC Beacon 200 Part No. Description 18-0061RK Cable bushing 18-0107RK Conduit Hub (3/4 in.