Sizing Cables
Battery cables (sold separately) should be appropriately sized to handle the expected load.
Please refer to the following table for the ampacities of copper cables with di󰀨erent gauge
sizes.
Copper Cable Gauge Size (AWG/mm
2
) Ampacity (A)
14 (2.08) 20
12 (3.31) 25
10 (5.25) 35
8 (8.36) 50
6 (13.3) 65
4 (21.1) 85
2 (33.6) 115
1 (42.4) 130
1/0 (53.5) 150
2/0 (67.4) 175
4/0 (107) 230
The above values are from the NEC Table 310.15(B)16 for copper cables rated at 75°C
(167°F), operating at an ambient temperature of no more than 30°C (86°F). Lengths in excess
of 6 feet (1829 mm) may require heavier gauge cable to avoid excess voltage drop in under-
sized wiring.
Connecting Batteries in Bank
DO NOT connect batteries in series. Doing so can cause catastrophic failure.
DO NOT connect batteries with di󰀨erent chemistries, rated capacities, nominal voltages,
brands, or models in parallel.
Please avoid excessive voltage di󰀨erence between parallel connected batteries to avoid
triggering the over-current protection.
The cables between each parallel connected battery should be of equal length to ensure
that all batteries can work equally together.
DO NOT connect more than 8 batteries in parallel.