FOR YOUR SAFETY If you smell gas: 1. Open windows. 2. DO NOT try to light any appliance. 3. DO NOT use electrical switches. 4. DO NOT use any telephone in your building. 5. Leave the building. 6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions. 7. If you cannot reach your gas supplier, call the Fire Department. WARNING Fire Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
TABLE OF CONTENTS SECTION 1: Heater Safety...................................................... 1 1.1 Manpower Requirements ............................................. 1 SECTION 2: Installer Responsibility ..................................... 2 2.1 Wall Tag ....................................................................... 2 2.2 Corrosive Chemicals.................................................... 2 2.3 National Standards and Applicable Codes ..................
TABLE OF FIGURES Figure 1: Standard Reflector ..................................................... 4 Figure 2: One Side Reflector..................................................... 4 Figure 3: Two Side Reflectors ................................................... 4 Figure 4: Universal Shield, Position 1 ....................................... 5 Figure 5: Universal Shield, Position 2 ....................................... 5 Figure 6: Universal Shield, Position 3 .......................................
SECTION 1: HEATER SAFETY SECTION 1: HEATER SAFETY Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections. Installation, service and annual inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL SECTION 2: INSTALLER RESPONSIBILITY The installer is responsible for the following: • To ensure the system is designed in accordance with the parameters of the CRV-Series Design Manual (P/N 127500NA). • To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a local Building Inspector or Fire Marshal for guidance.
SECTION 3: CRITICAL CONSIDERATIONS SECTION 3: CRITICAL CONSIDERATIONS 3.1 Required Clearances to Combustibles Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazards. Combustibles are materials that may catch fire and include common items such as wood, paper, rubber, fabric, etc. Maintain clearances to combustibles at all times for safety.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses. 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect. * Protective Grille clearances are the same as Standard Reflector.
SECTION 3: CRITICAL CONSIDERATIONS NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses. 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses. 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES 4.1 Gas Codes The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company. United States: Refer to National Fuel Gas Code, ANSI Z223.1 - latest revision (same as NFPA 54). Canada: Refer to CAN/CGA B149.1 and B149.2: Installation Codes for Gas Burning Appliances. 4.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL SECTION 5: MAJOR COMPONENTS The figures in this section provide a general overview of component placement in a CRV-Series system. The location of some components such as supports and couplings is crucial for proper installation. Assemble the heater components as shown on Page 14, Figure 11. FIGURE 10: Major Component Descriptions Optional reflector configurations are shown on Page 4, Figure 1 through Page 6, Figure 9.
SECTION 5: MAJOR COMPONENTS FIGURE 10: Major Component Descriptions (Continued) Reflector Joint Reflector End Cap (Aluminum or Stainless Steel) Punch out center section to accommodate heat exchanger tube when necessary. Tube and Reflector Hanger with Clamp Package Position this hanger no more than 4" (10 cm) away from the burner. Tube and Reflector Hanger Suspend system from these hangers.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 10: Major Component Descriptions (Continued) www.rg-inc .com ue Choc Électriq Danger de le courant Débrancheravant toute électrique révision. l doit être Cet appareià une source de connecter mise á terre. courant avec ces r la Faute de suivre peut entraîne instructions choc électriques. mort ou les U.S.
SECTION 5: MAJOR COMPONENTS 5.1 Standard Parts List Table 1: Contents of CRV-Series Burner Carton Part No.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Control Packages and Accessories 10001501 Water Resistant Sensor 02770002 System Control URVCCM ROBERTS GORDON® ULTRAVAC™ Central Controller (with Modem Chip & Software) Includes: URVSC ROBERTS GORDON® ULTRAVAC™ Controller 10080142 Modem Chip 10081501 Outdoor Sensor 10080410 PC Connection Cable Package URVCCR ROBERTS GORDON® ULTRAVAC™ Central Controller (with RS-485 Converter & Software) Includes: URVSC ROBERTS GORDON® ULTRAVAC™ Controller 10080430 RS-4
SECTION 6: DESIGN REQUIREMENTS SECTION 6: DESIGN REQUIREMENTS The CRV-Series system’s design is related to the system operation and performance required by the building being heated. Every effort should be made to follow the dimensions on the layout drawing. If deviations are necessary, either contact the company responsible for the layout design, your ROBERTS GORDON® independent distributor, or consult the CRV-Series Design Manual (P/N 127500NA).
14 S Coupling Relay* Exhaust to Outside Reflector with Hole * May not be needed with certain pumps and controllers. Refer to wiring diagram in the appropriate controller's Installation, Operation and Service Manual for details. **System Control requires thermostats. ROBERTS GORDON® ULTRAVAC requires zone sensors and additional control equipment. See the appropriate controller installation manual for details.
SECTION 7: HEATER INSTALLATION SECTION 7: HEATER INSTALLATION Do not locate the gas or electric supply lines directly over the path of the flue products from the heater. The heater must be installed in a location that is readily accessible for servicing. The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this instruction manual. The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 7.1 Tube Installation NOTE: Tubing requires a downward slope of 1/2" (13 mm) per 20' (6 m) away from burner. Tailpipe tubing requires a downward slope of 1" (26 mm) per 20' (6 m) away from burner. End View Combustion Chamber Weld Seam Bottom of Tube Tube 7' 6" (229 cm) Hanger 10' maximum (3 m) Turnbuckles Combustion Chamber Description Tube Turnbuckle Tube/Reflector Hanger Part Number 91409XXX 91903201 03090100 Step 7.
SECTION 7: HEATER INSTALLATION Step 7.2.1 Coupling and Tube Assembly (Continued) Tighten slide bar as shown below. Drive slide bar until tight. End of slide bar should be within tolerance listed below. ± 2" (5 cm) Correct Slide Bar Dimensions Incorrect Slide Bar Position Repeat Step 7.2, A - D until all tubes are assembled. NOTE: If coupling is not tight, loss of vacuum can occur. 7.3 Elbow Package Configuration Step 7.3.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 7.4 Reflector Installation Step 7.4.1 Reflector Installation with Hole Reflector with Hole Slide Reflector with hole through hanger. Unhook combustion chamber from chain and insert through hole. Reconnect chain. Hanger Tube Description Tube/Reflector Hanger Tube Reflector with Hole Part Number 03090100 91409XXX 02750304 Combustion Chamber Step 7.4.
SECTION 7: HEATER INSTALLATION Step 7.4.3 Reflector, U-Clip and Reflector Support Installation The pictorial drawings of the heater construction in reflector supports and U-clips depend on the Section 7 are schematic only and provide a general individual installation. Use either pop rivets or sheet guideline of where hangers, reflector supports and metal screws instead of u-clips when installing end U-clips are to be installed.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 7.5 Burner Installation Burner Burner Combustion Chamber Gasket End Vent Combustion Chamber Description Bolt Burner Lock Washer Gasket End Vent 20 Part Number 94273914 0270XXXX 96411600 01367800 013676XX End Vent Clips End Vent Rating Number NOTE: Install end vent at end combustion chamber position only.
SECTION 8: OPTIONAL HEATER ACCESSORIES SECTION 8: OPTIONAL HEATER ACCESSORIES Step 8.1 Tee Installation Tube Coupling Tee Description Tee Tube/Reflector Hanger Tube Coupling Part Number 01330XXX 03090100 91409XXX 01312700 Step 8.2 Reflector Joint Step 8.2.1 Reflector Joint Installation Reflector Reflector Joint Flatten Edge Scribe Contour 1" (2.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 8.2.2 Reflector Joint Installation Cut away contour with tin snips. Punch/drill six 3/32" (2 mm) holes. Step 8.2.3 Reflector Joint Detail Install reflector end cap. Attach reflector joint with six #8 sheet metal screws.
SECTION 8: OPTIONAL HEATER ACCESSORIES 8.3 Reflector Side Extension Step 8.3.1 Bracket Installation Tube Reflector Tube and Reflector Hanger Reflector Support Reflector Side Extension Bracket (2 per reflector) Use additional supports in high air movement applications. Description Reflector Side Extension Package Reflector Side Extension Retainer Clips Sheet Metal Screws Part Number 02712700 01368000 02751200 94118106 Order Separately Reflector Side Extension Bracket 01329910 Step 8.3.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 8.4 Universal Shield Universal shields are adjustable aluminum reflectors whose angle and height can be adjusted to direct heat to or away from a desired area. See Page 5, Figure 4 through Page 5, Figure 6 for positions.
SECTION 8: OPTIONAL HEATER ACCESSORIES 8.6 Two-Foot Decorative Grille Installation Step 8.6.1 Grille Installation Tube and Reflector Hanger Reflector Heat Exchanger Tube 2' x 4' (60 cm x 120 cm) Aluminum Grille Suspended Ceiling Frame Description Part Number Aluminum Grille 2' x 4' (60 cm x 120 cm) 91407000 Step 8.6.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 8.6.3 Reflector Side Extension Installation for Decorative Grilles NOTE: If the decorative grille system is to be installed in an area with considerable air movement, it is recommended that one #8 x 3/8" sheet metal screw be installed per reflector extension to 6" (15 cm) Minimum prevent it from blowing over. Cut relief notches for tube and reflector hangers.
SECTION 8: OPTIONAL HEATER ACCESSORIES Step 8.7.2 Decorative Grille Spread apart brackets and install decorative grille. Description Decorative Grille 8' x 1' (2.4 m x .3 m) Part Number 91406700 Step 8.7.3 Joint Piece and Reinforcement Joint Piece Slip joint piece into support bracket and fasten to bracket on one side of the joint only.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 8.7.4 End Piece and Reflector End Cap Reflector End Cap End Piece Insert end piece between grille and brackets. Fasten end piece to brackets using two #8 sheet metal screws and replace reflector end cap. Description End Piece Part Number 01365901 Step 8.7.5 90° Elbow Inside Corner Grille Brackets Joint Piece Insert end piece between grille and brackets. Decorative Grille Brackets 28 Cut grille bracket at reflector joint piece.
SECTION 8: OPTIONAL HEATER ACCESSORIES 8.8 Protective Grille Installation Step 8.8.1 Silicone Cap Installation Silicone Cap Description Grille Section Grille End Cap Silicone Cap Grille Finger Part Number 08050001 08050002 91915951-6P Step 8.8.2 Grille End Cap Installation B A Grille Grille End Cap C D Bend up 90° Pull outward Step 8.8.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Step 8.9 Classic Cast-Iron Components WARNING Suspension Hazard Hang heater with materials with a minimum working load of 750 lbs. (340 kg). Use special tube and reflector hangers when suspending the schedule 40 steel pipe system. Schedule 40 steel pipe is heavy and will fall if not supported properly. Distance between supports must be 7' (2.13 m) or less. Failure to follow these instructions can result in death, injury or property damage.
SECTION 9: PUMP INSTALLATION AND VENTING SECTION 9: PUMP INSTALLATION AND VENTING 9.1 Pump Installation For complete pump installation, please refer to the EP-100, EP-200 or EP-300 Series Installation, Operation and Service Manuals. FIGURE 14: EP-200 Condensate Valve Assembly Wall Description Condensate Valve Assembly Part Number 01327001 1" NPT threaded hole. Use 1" x ¾" reducer. (not supplied) Copper or galvanized pipe between pump and condensate valve. 36" (.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 9.2 General Venting Requirements Model EP-100, EP-200 and EP-300 Series Pumps WARNING Carbon Monoxide Hazard Heaters installed unvented must be interlocked with sufficient building exhaust. Heaters must be installed according to the installation manual. Failure to follow these instructions can result in death or injury.
SECTION 9: PUMP INSTALLATION AND VENTING FIGURE 15: Vertical Venting Configuration Approved Vent Cap 2' (.6 m) Minimum Approved Thimble Flexible Boot Aluminized Tee Clamps Part Number Drain Cap Description Part Number 1" (2.5 cm) P.V.C to drain system in accordance with local codes. 6"(1.5 cm) 20"(5.1 cm) for EP-300 Description 01330203 Tee, 4" (10 cm) Aluminized 91409403 Tube, Aluminized 4" (10 cm) dia.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 9.3 Horizontal Venting 4" (10 cm) Pipe FIGURE 16: EP-100 Horizontal Venting Configurations 18" (46 cm) Minimum 40" (102 cm) Maximum Bird Screen 4" (10 cm) Single Wall Pipe 25' (8 m) and 3 Elbows Maximum Approved Thimbles 4" (10 cm) Band Clamp 18" (46 cm) Minimum 40" (102 cm) Maximum Pitch single wall pipe downward away from pump 1/4" (6 mm) for every 10' (3 m). Vent Terminal Tjernlund VH1-4 5" to 4" Reducer (12.
SECTION 9: PUMP INSTALLATION AND VENTING FIGURE 17: EP-200 Series Horizontal Venting Configurations 18" (46 cm) Minimum 40" (102 cm) Maximum Bird Screen 4" (10 cm) Single Wall Pipe Approved Thimbles 4" (10 cm) 18" (46 cm) Minimum - Band Clam 40" (102 cm) Maximum 10' (3 m) Maximum and No Elbows 4" (10 cm) Vent Terminal Pitch single wall pipe downward away from pump 1/4" (6 mm) for every 10' (3 m). Vent Terminal Tjernlund VH1-4 5" to 4" Reducer (12.5 cm to 10 cm) 6" to 5" Reducer (15 cm to 12.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 18: EP-300 Series Horizontal Venting Configurations 18" (46 cm) Minimum 40" (102 cm) Maximum 10' (3 m) Maximum and 1 Elbow 6" (15 cm) Bird Screen (Included) 10' (3 m) Maximum and 1 Elbow Single Wall Pipe/Tube 6" (15 cm) Pitch single wall pipe downward away from pump 1/4" ( 6 mm) for every 10' (3 m).
SECTION 10: OUTSIDE AIR SUPPLY SECTION 10: OUTSIDE AIR SUPPLY The CRV-Series system is approved for use with an outside air system. Halogenated hydrocarbons or other corrosive chemicals in the air can be drawn into the equipment and seriously damage the system components. Avoid the use of such chemical compounds near the air inlet to the heaters.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 10.3 Outside Air Blower Internal Wiring FIGURE 20: Outside Air Blower Internal Wiring Diagram Outside air blower is shipped with the blower manufacturer’s standard internal wiring. For use with Roberts-Gordon heaters, the outside air blower must be rewired with existing wires by the electrical contractor. See diagram. BLOWER PRESSURE SWITCH C Internal 24 V transformer provided will not be used and can be discarded.
SECTION 10: OUTSIDE AIR SUPPLY FIGURE 22: Air Supply Blower Support 5" (12.5 cm) Inlet Pipe Outside Air Supply Blower Bird Screen or Vent Cap Outside Wall Wall 5" (12.5 cm) Outlet Pipe Description Blower 5" (12.7 cm) Vent Cap 6" (15 cm) Bird Screen 6" (15 cm) Band Clamp Part Number 90707501 90502302 01397400 91913703 Description Filter Housing 4" (10 cm) Take Off Blower 5" (12.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 24: Non-Pressurized Outside Air Supply Description Pressure Switch Kit 4" (10 cm) Bird Screen 4" (10 cm) Vent Cap 6" (15 cm) Vent Cap Vent Cap Pressure Switch or Bird Screen Lock Nuts 6' (1.8 m) Maximum Outside Wall 40 7/16" (11.
SECTION 11: GAS PIPING SECTION 11: GAS PIPING There is an expansion of the tube with each firing cycle. This will cause the burner to move with respect to the gas hose. This can cause a gas leak resulting in an unsafe condition if the gas connection is not made in strict accordance with Figure 25. Meter and service must be large enough to handle all the burners being installed plus any other connected load.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL SECTION 12: CONTROL METHODS WARNING Electrical Shock Hazard Disconnect electrical power and gas supply before servicing. This appliance must be connected to a properly grounded electrical source. Failure to follow these instructions can result in death or electrical shock. There are several methods of controlling CRV-Series systems. The options are as follows: 12.
SECTION 12: CONTROL METHODS FIGURE 26: One Zone Operation without Control Panel SPST (12A) Transformer Relay R C W G Y Thermostat Black 120 V 1Ø 60 Hz 1 2 4 COIL L Black N White 5 3 6 COIL Ground Red Pump Motor L L N Pressure Switch (Pump) Description SPST Transformer Relay N Zone 1 Burners Nine Burners Maximum Part Number 90417600 43
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 27: One Zone Operation (with Outside Air Blower) without Control Panel SPST (12 A) Transformer Relay R C W G Y Thermostat Black 120 V 1Ø 60 Hz Outside Air Blower 1 2 4 COIL L Black N White 5 3 6 COIL Ground N L Pressure Switch (Outside Air Blower) Red L L Pressure Switch (Pump) N N Pump Motor Zone 1 Burners Nine Burners Maximum 44
SECTION 12: CONTROL METHODS FIGURE 28: Two Zone Operation without Control Panel DPST (12 A) Transformer Relay DPST (12 A) Transformer Relay R W G C R C W G Y Y Zone 2 Thermostat Zone 1 Thermostat Purple 1 4 COIL 3 2 6 COIL 5 Red 1 Purple 2 4 COIL Red 5 3 6 COIL Black 120 V 1Ø 60 Hz Black Black Red/Yellow White White L Red/Yellow Black N L L L N N Pump Motor Pressure Switch (Pump) Description DPST Transformer Relay N Zone 1 Burners Zone 2 Burners Nine Burners Total Maximu
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 29: General System Wiring Burner Receptacles 4 Zone Max Pressure Switch Pump Motor 115 Vac Operation (230 Vac Operationseparate power circuit required for EP-203 or EP-300 series pumps) Thermostats Motor Starter (Needed for EP-203 and EP-300 Series Pump) Outside Air Supply Blower Motor and Pressure Switch 120 V 1Ø 60 Hz L N 120 Vac Maximum 20 Amps Total FIGURE 30: External Wiring Diagram EP-100 and EP-201 120 V 1 Ø Pump Pump All burners
SECTION 12: CONTROL METHODS FIGURE 31: External Wiring Diagram EP-301 120 V 1 Ø Pump EP 301 Pump All burners must be connected to Ground. (Not shown.) Zone 1 Zone 2 Zone 3 Zone 4 6 4 Do not directly connect the controller relay terminals to the pump motor. Product damage will result. IEC contactor (P/N 10050009) rated for the EP 301 pump motor The power supply for the pump must be separate from the controller supply.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 33: Burner Internal Wiring TRANSFORMER White Black 120 V Power Supply Green Green GAS VALVE 1 5 3 4 Yellow Blue Yellow TH Brown Yellow V1 S1 V2/GND Black IGNITION MODULE BURNER If any of the original wire as supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and 600 volts.
SECTION 13: STARTING THE SYSTEM SECTION 13: STARTING THE SYSTEM Start with the main gas valve closed and the electric power off. 13.1 Checking the Gas Line 1. Open the main valve and verify that no gas is flowing through the meter. 2. Purge the line if this was not done following pressure testing with air. 3. Verify that the gas pressure is not above 14'' w.c. (1/2 PSIG). 4. Close the main gas valve. 13.2 Checking the Electrical System 1. See that all temperature setpoints are set below room temperature.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL FIGURE 35: Vacuum Reading Combustion Chamber at end position End Vent Insert tubing about 6" (15 cm). Manometer 6 5 4 3 2 1 0 1 2 3 4 5 6 Approximate reading after adjusting damper couplings and pump inlet. (~ ~2.5"- 3.0" w.c.
SECTION 14: OPERATION AND MAINTENANCE SECTION 14: OPERATION AND MAINTENANCE The heater is equipped with a direct-spark ignition system. 14.1 Sequence of Operation 1. Turn the thermostat up. When the thermostat calls for heat, the pump will start immediately. After a short period, the burners will begin their ignition sequence. Sparking will begin at the electrodes and the gas valve will be energized 45 seconds later. 2. The flame will be sensed by the flame sensing rod and the electrode is de-energized. 3.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 14.5 Maintenance Checklist WARNING Explosion Hazard Service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier. Turn off gas and electrical supplies before performing service or maintenance.
SECTION 14: OPERATION AND MAINTENANCE Tubes Make sure there are no cracks. Make sure tubes are connected and suspended securely. See Page 15, Figure 12 through Page 17, Section 7.2.1. Make sure there is no dirt, sagging, bending or distortion. Clean or replace as required. Gas Line Check for gas leaks. See Page 41, Figure 25. Combustion Chamber Window Make sure it is clean and free of cracks or holes.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL Pump With pump operating, check for excessive vibration or noise. Vibration is usually a sign that the impeller is out of balance. Turn off the system, insure power is shut off and remove the inlet plate. Check the shaft seal and replace it if worn or missing. With the Power off: Check the inlet and outlet of the pump for blockage or excessive soot and clean as necessary. Check boots for cracking or deterioration and replace if necessary.
No Do all the burners ignite smoothly? Yes Yes No After 45 seconds pre-purge period, do the burners light? No Yes Turn up thermostat. Does the pump turn on? START Is the motor hot? Wrong end vent plate may be installed. Make sure plate and burner match. No Is the vacuum setting too high? Refer to control panel list. No Yes Refer to control panel manuals list. Yes Is there power to the zone? Adjust system for proper vacuum at the end vent.
56 No No Yes TROUBLESHOOT ENDS. If problems persist, contact No your ROBERTS GORDON® Independent Distributor. Yes Does the pump shut down after a 2 minute post-purge period? Yes Do burners shut off after the call for heat is satisfied? No Is the flame low? No Is the system leaking water? Yes No Do the burners lockout intermittently? Yes Contact Roberts-Gordon at www.rg-inc.com Make sure that all thermostats or internal sensors are satisfied.
SECTION 16: REPLACEMENT PARTS SECTION 16: REPLACEMENT PARTS Use only genuine ROBERTS GORDON® replacement parts. Use of parts not specified by Roberts-Gordon voids warranty. Failure to follow these instructions can result in property damage.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL SECTION 17: GENERAL SPECIFICATIONS 17.1 Material Specification 17.1.1 Reflectors .024 Aluminium (Optional - 024 Stainless Steel Type 304). 17.2 Heater Specifications 17.2.1 Ignition Fully Automatic, Three-Try, Direct Spark, Electronic Ignition Control, 100% Safety Shut-Off. 17.3 Suspension Specifications Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 15, Figure 12. 17.
SECTION 17: GENERAL SPECIFICATIONS General Specifications for pumps are as follows: Pump Dimensional Data (in.) Model A B EP-100 17 14.5 EP-201/203 17.75 17 EP-301/303 25.6 24.8 C 21 20.25 22.7 D 3.75 3.25 4.8 E 10 10 15.2 F 4 4.5 6 G 4 4.5 6 G A D E B C F dia.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL 60
SECTION 18: THE ROBERTS GORDON® CORAYVAC® LIMITED WARRANTY SECTION 18: THE ROBERTS GORDON® CORAYVAC® LIMITED WARRANTY The data plate and/or serial number are removed, ROBERTS-GORDON WILL PAY FOR: defaced, modified or altered in any way. Within 42 months from date of shipment from RobertsThe ownership of the CORAYVAC® is moved or Gordon, replacement parts will be provided free of transferred. This warranty is nontransferable.
® OWNER WARRANTY REGISTRATION CARD Mail or Fax to: Roberts Gordon, LLC 1250 William Street, P.O. Box 44 Buffalo, NY 14240-0044 Phone: 716-852-4400 Fax: 716-852-0854 Toll Free: 800-828-7450 www.rg-inc.
Attach this information to a wall near the ROBERTS GORDON® heater. ® I n f r a r e d H e a t i n g Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service. Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.