Service manual

ROBERTS GORDON
®
NRG CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
20 of 40
5.3.2 Default Settings
The following settings are factory defaults and will be active following a system reset.
Function Section Default Setting
Network Setting Stand Alone
Network Defaults
Network Access Code 5.6.1 Empty
Network Configuration Code 4143 Fixed
Network ID 5.6.1 00
Control Name 5.6.1 Empty
Network Access 5.6.1 Full
Burner Lockout Reset from
Network
5.6.1 Off
Manager Setting Defaults
Manager Access Code 5.5.4 0000
User Access Code 5.5.4 0000
Daytime Temperature 5.5.2 20° C
Night Temperature 5.5.2 04° C
Operating Times 5.5.3 08:00 17:00 Mon - Fri OFF Sat - Sun
Engineer Setting Defaults
Engineer Access Code 6343 fixed
Optimisation On
Rate of Change 5.6.2 On 15 minutes / °
Maximum Pre-Heat Hours 02
Burner Operation On/Off
Burner Modulation Off
Differential 5.6.3 02°
Double Ignition 0 OFF (Always Leave OFF)