O p e r a t i n Operating Manual Manual de funcionamiento Manuel d’utilisation Manuale per l’uso Bedienungsanleitung g M a n u a l Not for use in automotive R-134a applications.
Model 25201B Refrigerant Recovery Unit, 230V Design Pressure: 336 psig — 435 psig SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT, and NOTE messages in this manual. These messages are defined as follows: WARNING means you may risk serious personal injury or death; CAUTION means you may risk personal injury, property damage, or unit damage; IMPORTANT means you may risk unit damage; and NOTEs and operating Tips provide clarity and helpful information.
Introduction Table of Contents Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Operating Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . 2 Setup Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . 4 Recovery Procedure . . . . . . . . . . . . . . . . . . . . . .
Setup Instructions Operating Guidelines • The voltage at the unit must be ±10% of the unit’s rated voltage. • Extension cords must be a minimum of 14 AWG and kept as short as possible. • To minimize mixing of refrigerants, the self-clearing procedure must be performed after each recovery operation. • The low-side gauge on the unit allows you to monitor system pressure and stop recovery when a deep enough vacuum has been reached. The high-side gauge allows you to monitor the refillable tank pressure.
Setup Instructions Liquid Indicator Tank Pressure System Pressure High Pressure Indicator Circuit Breaker Selector Switch This is a two-position switch: Recover—Self-Clear Power Switch Front View of Unit Hose Connections 553074 Rev.
Operating Instructions Recovery Procedure WARNING To prevent personal injury, Read and follow all warnings at the beginning of this manual before operating the unit. Wear safety goggles when working with refrigerants. Use only authorized refillable refrigerant tanks. Disconnect hoses using extreme caution. All hoses may contain refrigerant under pressure. 1. Connect hoses as described in the Setup Instructions. 2. Open the LIQUID and VAPOR valves on the recovery tank. Open the ball valves on all four hoses.
Operating Instructions WARNING The refrigerant level in the tank must not exceed 80% of the tank volume. Failure to monitor the level could result in excessive hydrostatic pressures, causing physical injury or death. tank-to-tank transfer When recovering refrigerant from one refillable tank into another, the color of the hoses used for SYSTEM LIQUID and SYSTEM VAPOR may not match the color of the liquid and vapor valves on the tank you are pulling the refrigerant from.
Operating Instructions Self-Clearing Procedure CAUTION! Do not mix refrigerant types. Always perform the selfclearing procedure after each recovery. Beginning each job with a “clean” unit will help eliminate mixing of different refrigerant types. 1. Close the ball valves on the red and blue hoses connected to the A/C-R system. Disconnect these hoses from the system’s access ports. 2. Close the blue LIQUID valve on the tank and the ball valve on the blue TANK LIQUID hose.
Maintenance This unit has been designed for minimal maintenance. The compressor should be evaluated for wear after 2,500 hours of use. Call Robinair’s Technical Support Line, (800) 822-5561, for the location of an authorized Robinair service center near you.
Troubleshooting Tips Compressor does not start Problem: Compressor circuit breaker has tripped. Solution: Depress the circuit breaker switch. Problem: HIGH PRESSURE light is on. Solution: The high side pressure switch has tripped; verify the tank and hose ball valves are open. Check tank and verify it is not full. Problem: Power switch is not on. Solution: Press the power switch to ON. Compressor runs but does not move refrigerant Problem: The ball valves on the hoses are not open.
Flow Diagram 553074 Rev.
Wiring Diagram 10
Conversion Table CONVERSION TABLE 553074 Rev. A April 9, 2009 OZ. LBS. 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0 14.5 15.0 15.5 16.0 0.03 0.06 0.09 0.13 0.16 0.19 0.22 0.25 0.28 0.31 0.34 0.38 0.41 0.44 0.47 0.50 0.53 0.56 0.59 0.63 0.66 0.69 0.72 0.75 0.78 0.81 0.84 0.88 0.91 0.94 0.97 1 lb.
Warranty Robinair Limited Warranty Statement Rev. November 1, 2005 This product is warranted to be free from defects in workmanship, materials, and components for a period of one year from date of purchase. All parts and labor required to repair defective products covered under the warranty will be at no charge. The following restrictions apply: 1. The limited warranty applies to the original purchaser only. 2.
Visit our web site at www.robinair.com or call our toll-free Technical Support Line at 800-822-5561 in the continental U.S. or Canada. In all other locations, contact your local distributor. To help us serve you better, please be prepared to provide the model number, serial number, and date of purchase of your unit. To validate your warranty, complete the warranty card attached to the unit, and return it within ten days from date of purchase.
655 Eisenhower Drive Owatonna, MN 55060-0995 USA Tech Services Fax Customer Service Fax 800 412 800 800 822 690 533 322 5561 2001 6127 2890 www.robinair.com 553074 (Rev.