Safety Recommendations
42 Advanced Digital Motor Controller User Manual V2.0, July 8, 2019
3. Check that there is no STO fault present (through Roborun+ Utility/Serial)
4. Deactivate STO 1 and STO 2 (both logic level 1)
5. Check that STO is not active and that there is no STO fault present (through Robo-
run+ Utility/Serial).
SAFETY INSTALLATION
It is required that the controller has to be placed in an enclosure that can provide
IP54 protection.
SAFETY REGISTRATION
It is required that STO end user should follow up www.roboteq.com and register to
site/forum for any news about safety function.
STO Voltage source specification attention
In order to have maximum response at STO implementation, user/installer/integrator
should use voltage source with low output capacitance. In any other case, latency in acti-
vation might occur.
Compliance and Safety Metrics
The STO function is compliant to:
IEC 61800-5-2:2007, SIL 3
IEC 61508:2010, SIL 3
IEC 62061:2005, SIL 3
ISO 13849-1:2015, Category 3 Performance Level e
Metric acc. To IEC 61508, IEC 61800-5-2,
IEC 62061
Value
SIL Up to 3
PFH 5 FIT
Mission Time and Proof Test Interval 20 years
Performance Level e
Category 3
MTTFD >100 years