Data Sheet

4 FIM2360 Motor Controller Datasheet Version 1.0 July 20, 2018
Controller Power
Motor Wires
VMot Ground Ground
(top)
Power Control
VMot
PwrCtrl
SW1 Main
On/Off Switch 1A
F2
1A
Diode
>20A
Resistor
1K, 0.5W
+-
SW2
Emergency
Contactor or
Cut-off Switch
F1
Encoder
Connector
I/O Connector
Ground
Ground
Main
Battery
Backup
Battery
Note 6
Do not Connect!
Note 1
2 etoN 3 etoN
U1 U2 V1 V2 W1 W2
Note 5
Note 4
Motor1
Encoder 1
A1/B1/
GND/+5V
U1
V1 W1
Motor2
Encoder 2
A2/B2/
U2
V2 W2
U1
V1
W1
U2
V2
W2
FIGURE 3. Powering the controller. Thick lines identify MANDATORY connections
Important Warning
Carefully follow the wiring instructions provided in the Power Connection section of the User Manual. The
information on this datasheet is only a summary.
Mandatory Connections
It is imperative that the controller is connected as shown in the above diagram in order to ensure a safe and trou-
ble-free operation. All connections shown as thick black lines line are mandatory. The controller must be powered
On/Off using switch SW1on the Pwr Ctrl tab. Use a suitable high-current fuse F1 as a safety measure to prevent
damage to the wiring in case of major controller malfunction.
Emergency Switch or Contactor
The battery must be connected in permanence to the controllers VMot tabs via a high-power emergency switch
or contactor SW2 as additional safety measure. The user must be able to deactivate the switch or contactor at
any time, independently of the controller state.
Electrostatic Discharge Protection
In accordance with IEC 61000-6-4, Roboteq Motor Controllers are designed to withstand ESD up to 4kV touch
and 8kV air gap. This protection is implemented without any additional external connections required.
Some specifications, such as EN12895, require a higher level of protection. To maximize ESD protection, up to
8kV touch and 15kV air gap, you may connect the metallic heatsink of the controller to your battery negative ter-
minal. See App Note 062918 for example connections.