Schematic

Using the Roborun Configuration Utility
368 Advanced Digital Motor Controller User Manual V1.8, August 28, 2017
Selection List
Text String
When entering a numerical value, that value is checked against the allowed minimum and
maximum range for that parameter. If the entered value is lower than the minimum, then
the minimum value will be used instead, if above the maximum, then the maximum value
will be used as the entered parameter.
Boolean parameters, such as Enabled/Disabled will appear as a two-state menu list.
Some parameters, like Commands or Actions have the option to apply to one or the other
of the motor channels. For this type of parameters, next to the menu list are checkboxes –
one for each of the channels. Checking one or the other tells the controller to which chan-
nel this input or action should apply.
FIGURE 20-5. Parameter applying to one or more tabs channels
String parameters are entered in plain text and they are checked against the maximum
number of characters that are allowed for that string. If entering a string that is longer, the
string is truncated to the maximum number of allowed characters.
Important Notice about Decimals
The use of Period vs Coma when entering a decimal configuration value depends
on the regional settings of Windows. On USA PC’s, use periods. On European PC’s
use comas. If unsure, load the configuration back from the controller after changing
and saving. Verify that the value that was stored in the controller is the one that was
entered.
Automatic Analog and Pulse input Calibration
Analog and Pulse inputs can be configured to have a user-defined minimum, maximum
and center range. These parameters can be viewed and edited manually by expanding the
Range subnode.
The minimum, maximum and center values can also be captured automatically by clicking
on the “Calibrate” link.
FIGURE 20-6. Min/Max/Center parameters and auto calibrations for Analog and Pulse inputs