300 Advanced Digital Motor Controller User Manual V2.1, December 3, 2020
ond priority belongs to the CAN mode. Each priority item is then one of the three (four)
command modes: Serial, Analog (Spektrum) or RC Pulse. See Command Priorities in the
User Manual. Default prority orders are: 1-Serial, 2-Pulse, 3-None.
Syntax Serial: ^CPRI pp nn
~CPRI [pp]
Syntax Scripting: setconfig(_CPRI, pp, nn)
Number of Arguments: 2
Argument 1: Level
Min: 1 Max: 3 or 4
Default: See description
Argument 2: Command
Type: Unsigned 8-bit
Min: 0 Max: 2 or 3
Default: See description
Where:
pp = Priority rank
nn =
0: Serial
1: RC
2: Analog (or Spektrum)
3: None (or Alalog)
4: None
Example:
^CPRI 1 2 : Set Analog as first priority
~CPRI 2 : Read what command mode is second priority
Note:
USB, RS232, RS485 and TCP commands share the “Serial” type. When serial commands
come from different Serial source, they are executed in the order received.
DFC - Default Command value
HexCode: 0E
Description:
The default command values are the command applied to the motor when no valid com-
mand is fed to the controller. Value 1001 causes no change in position at power up until a
new position command is received
Syntax Serial: ^DFC cc nn
~DFC [cc]
Syntax Scripting: setconfig(_DFC, cc, nn)
Number of Arguments: 2