334 Advanced Digital Motor Controller User Manual V2.1, December 3, 2020
Syntax Scripting: setconfig(_ATRIG, cc, nn)
Number of Arguments: 2
Argument 1: Channel
Min: 1 Max: Total Number of Motors
Argument 2: Level
Type: Unsigned 16-bit
Min: 10 Max: Max Amps in datasheet
Default: Max Amps rating in datasheet
Where:
cc = Motor channel
nn = Amps *10
Example:
^ATRIG2 550: Set Amps Trigger to 55.0A
BKD - Brake Delay
HexCode: 01
Description:
Set the delay in miliseconds from the time a motor stops and the time an output connect-
ed to a brake solenoid will be released. Applies to any Digital Ouput(s) that is configured
as motor brake. Delay value applies to all motors in multi-channel products.
Syntax Serial: ^BKD nn
~BKD
Syntax Scripting: setconfig(_BKD, nn)
Number of Arguments: 1
Argument 1: Delay
Type: Unsigned 16-bit
Min: 0 Max: 65536
Default: 250 = 250ms
Where:
nn = Delay in milliseconds
Example:
^BKD 1 1000 : Causes the digital output to go off, and therefore activate the brake, 1.0s
after motor stops being energized
BPR - Bypass Trajectory/Ramp
HexCode: F3
Description:
This parameter is configured in order to be able to bypass the ramp of the command or
the trajectory in case of position mode. It is applicable mainly in torque mode (in case it
requires high transitions) or in DS402 cyclic sync modes.