Data Sheet
Use of Safety Contactor for Critical Applications
SDC3260 Motor Controller Datasheet 5
Note 5: Connect the controller’s bottom plate to a wire connected to the Earth while the
charger is plugged in the AC main, or if the controller is powered by an AC power supply.
Note 6: Beware not to create a path from the ground pins on the I/O connector and the
battery minus terminal.
Use of Safety Contactor for Critical Applications
An external safety contactor must be used in any application where damage to property
or injury to person can occur because of uncontrolled motor operation resulting from fail-
ure in the controller’s power output stage.
FIGURE 3. Contactor Wiring Diagram
The contactor coil must be connected to a digital output configured to activate when
“No MOSFET Failure”. The controller will automatically deactivate the coil if the output is
expected to be off and battery current of 1A or more is measured for more than 0.5s. This
circuit will not protect against other sources of failure such as those described in the “Im-
portant Safety Disclaimer” on Page3.
Controller Mounting
During motor operation, the controller will generate heat that must be dissipated. The
published amps rating can only be fully achieved if adequate cooling is provided. Good
conduction cooling can be achieved by mounting the controller to a metallic surface, such
as the chassis, cabinet, etc.
PwrCtrl
SW1 Main
On/Off Switch 1A
F2
1A
Diode
>20A
Resistor
1K, 0.5W
+-
F1
I/O Connector
VMot
to +40V Max
Digital Out
Ground
Ground
Main
Battery
FIGURE 1.Contactor wiring diagram