Technical data
Series F2 80 C
22 Ed. 06/2011
Figure 5 – Installation type C13 with mixing chamber (optional) with separate pipes Ø 130
Figure 6 – Installation type C13 with mixing chamber (optional) with air pipe Ø 80 and flue pipe Ø 110
MAXIMUM ALLOWED LENGTHS (m)
AIR PIPE Ø
130
FLUE PIPE Ø
130
F2 80 C 20* 20*
MAXIMUM ALLOWED LENGTHS (m)
AIR PIPE
Ø 80
FLUE PIPE
Ø 110
F2 80 C 3 11
C13 WALL COAXIAL INSTALLATION W/Ø 130 PIPES
CAUTION: the above-listed lengths are applicable only if
the flue pipe follows a linear path as shown in
Figure.
Otherwise, you need to calculate
the relevant pressure drops
.
* For installations with pipes length more than 20 meters we
kindly advise to contact pre-sale service of Robur S.p.A.
INSTALLATION C13 C/AIR PIPE Ø 80 AND FLUE PIPE Ø 110
CAUTION: the above-listed lengths are applicable only if
the flue pipe follows a linear path as shown in
Figure.
Otherwise, you need to calculate
the relevant pressure drops
.
* For installations with pipes length more than 20 meters we
kindly advise to contact pre-sale service of Robur S.p.A.