Technical data

Series F2 80 C
28 Ed. 06/2011
CAUTION: the above-listed lengths are applicable only
if the air and flue pipes follow a linear path
as shown in Figure.
Otherwise, you need
to calculate the relevant pressure
drops
.
* For installations with pipes length more than 20 meters we
kindly advise to contact pre-sale service of Robur S.p.A.
Figure 17 – Installation type C53 with mixing chamber (optional) with pipes Ø 130
Figure 18 – Installation type C53 with mixing chamber (optional) with air pipe Ø 80 and flue pipe Ø 110
MAXIMUM ALLOWED LENGTHS (m)
AIR PIPE
Ø 130
FLUE PIPE
Ø 130
F2 80 C 20* 20*
MAXIMUM ALLOWED LENGTHS (m)
AIR PIPE
Ø 80
FLUE PIPE
Ø 110
F2 80 C 3 13
C53 INSTALLATION C/PIPES Ø 130
C53 INSTALLATION C/AIR PIPE Ø 80 AND FLUE PIPE Ø 110
CAUTION: the above-listed lengths are applicable only
if the air and flue pipes follow a linear path
as shown in Figure.
Otherwise, you need
to calculate the relevant pressure
drops
.
* For installations with pipes length more than 20 meters we
kindly advise to contact pre-sale service of Robur S.p.A.