Technical data
MAINTENANCE AND SERVICING 
Ed.06/2011  39
SECTION 5: MAINTENANCE AND SERVICING 
In this section you can find a few maintenance suggestions and the instructions which are 
necessary to technical assistants in order to adjust the gas valve and replace the gas. 
5.1  HOW TO ADJUST THE GAS VALVE 
For a correct operation of the F2 Series gas fired unit heaters it is necessary that the 
calibration values of the gas valve are equal to those indicated in the table here below. 
The appliance is sent from the factory with the gas valve already calibrated. If you need to 
adjust the gas valve, proceed as described here below. 
OFF-SET VALUES 
F2 80 
RATED OFF-SET  (mbar) 
(mmH
2
O)
-0,15
-1,5
MAXIMUM OFF-SET  (mbar) 
(mmH
2
O)
-0,09
-0,9
MINIMUM OFF-SET  (mbar) 
(mmH
2
O)
-0,25
-2,5
Table 8 – OFF-SET values
To Have: the heater installed and connected to the power and gas supply lines. 
  The gas valve adjustment must be performed by qualified personnel. To this 
regard, ROBUR S.p.A. can dispose of a network of Assistance Centres which can 
be reached through the point of sale, the local agent or by calling directly the 
Customer Assistance of ROBUR S.p.A. (tel. +39 035/888111). 
1 -  Connect a pressure gauge to the pressure connector A, after removing the relevant 
fastening screw (see Figure 25 at page 40). 
!
 In case of use of a differential pressure gauge, you need to connect the pressure 
connector A of the gas valve to the pressure gauge connector + (positive). 
2 -  Turn on the appliance and wait until the flame is stabilized (2 minutes 
approximately).
3 -  With door open, operate on the off-set adjusting screw C (see Figure 25 at page 40) 
until the rated value specified in Table 8 is obtained. 