Technical data
10
The appliance must never normally be switched on and off by shutting off the power 
supply upstream of the Controle Device (CCP, DDC or consent switch) before having used 
the latter first and waited for the shutdown cycle to end (approximately 7 minutes). The 
shutdown cycle terminates when the hydraulic pump switches off (no parts in motion).
Shutting off the power supply while the appliance is running can cause permanent dam-
ages to internal components!
If  the appliance  fails  to operate correctly,  with the  consequent  indication  of  the  Ma-
chine code, follow the instructions of Paragraph 9.1 OVERVIEW AND OPERATING CODES/
TROUBLESHOOTING → 82.
In the event of failure of the appliance and/or breakage of any component, do not at-
tempt to repair and/or restore operation; proceed as follows:
 shut off the appliance immediately (if possible and if no dangerous condition ex-•
ists) through the controls (CCP, DDC or permissive switch) and wait for the end of 
the cooling down cycle (around 7 minutes);
 immediately get in touch with Technical Assistance.•
Proper ordinary maintenance ensures the efficiency and good operation of the appli-
ance over time.
Carry  out  maintenance  operations  according  to  the  instructions  supplied  by  the 
manufacturer.
For the maintenance of internal components of the appliance, contact Technical Assist-
ance; for other maintenance requirements, see Paragraph 7.2 MAINTENANCE → 77.
Any repair of the appliance must be carried out by Technical Assistance, using only origi-
nal spare parts.
Failure to observe the indications above may compromise the operation and safety of the 
appliance, and may invalidate warranty.
If the appliance is to be disposed of, contact the manufacturer for its correct disposal.
If the appliance is to be sold or transferred to another owner, ensure that this “Installation, 
user and maintenance manual” is handed over to the new owner and installer.
3.2   NOTES ON OPERATION OF THE APPLIANCE
The appliance uses the water/ammoniac absorption thermodynamic cycle (H
2
0 – NH
3
) 
to produce hot water, drawing the required energy from the ground (GAHP-GS) or, in the 
case of the GAHP-WS, from ground water.
The water/ammonia thermodynamic cycle used in the unit GAHP-GS/WS is realized in 
a hermitically sealed circuit, directly verified by the manufacturer to ensure the perfect 
tightness of all joints, thus making refrigerant top-ups completely unnecessary.
Description and general characteristics
The GAHP-GS/WS is a modulating condensation heat pump: the thermal power modu-
lates from 100% to 50% depending on load, to ensure optimal comfort.
The water/water gas absorption heat pump GAHP-WS produces hot water to +65°C for 
heating purposes and up to +70°C for sanitary hot water.
The geothermal absorption heat pump GAHP-GS is available in the following versions: