Technical data

14
GAHP WS
Power supply
Voltage V 230
TYPE SINGLE PHASE
Frequency
50 Hz
supply
50
Electrical power absorption nominal kW 0,47 (5)
Degree of protection IP X5D
INSTALLATION DATA
Level of acoustic pressure at 10 meters (maximum) dB(A) 39 (7)
Minimum storage temperature °C -30
Maximum operating pressure bar 4
Maximum condensation water flow rate l/h 4,0
Water content inside the apparatus
HOT SIDE l 4
COLD SIDE l 3
Water fitting
TYPE F
thread " G 1 1/4
Gas fitting
TYPE F
thread " G 3/4
Safety valve outlet channel fitting " G 1 1/4
Fume outlet
Diameter (∅) mm 80
Residual head Pa 80
Product configuration C63
Size
width mm 848 (6)
height mm 1278
depth mm 690
Weight In operation kg 300
GENERAL INFORMATION
INSTALLATION MODE
C13, C33, C43, C53, C63,
C83, B23P, B33
COOLING FLUID
AMMONIA R717 kg 7,7
WATER H2O kg 10
MAXIMUM PRESSURE OF THE COOLING CIRCUIT bar 35
** in transient operation, lower temperatures are allowed.
Notes:
As per EN12309-2 evaluated on actual thermal capacity. For operating conditions 1.
other than nominal, refer to the Design Manual.
For flow rates different from the nominal refer to the Design Manual.2.
PCI 34.02 MJ/m3 (1013 mbar – 15 ° C).3.
PCI 46.34 MJ/kg (1013 mbar – 15 ° C).4.
± 10% depending on power voltage and absorption tolerance of electric motors.5.
Overall dimensions excluding fumes pipes (see Figure 3.1 Size 6. 15).
Free field, frontal, directionality factor 2.7.
Table 3.3 – PED data
GAHP GS LT GAHP GS HT GAHP WS
PED data
COMPONENTS UNDER PRESSURE
Generator l 18,6
Leveling chamber l 11,5
Evaporator l 3,7
Cooling volume transformer l 4,5
Absorber/condenser l 3,7
Cooling absorber solution l 6,3
Solution pump l 3,3
TEST PRESSURE (IN AIR) bar g 55
SAFETY VALVE PRESSURE CALIBRATION bar g 35
FILLING RATIO
kg of
NH3/l
0,137 0,159
"SEALED SYSTEM" TARE kg 165
FLUID GROUP GROUP 1°