Technical data

22
In the same way: 7. turn the knob to scroll through content (menus, parameters, ac-
tions), press the knob to select/confirm the content (access a menu, display/set
a parameter, execute an action, quit or return to the previous level). For example,
to quit the menus, turn the knob to scroll through menus "0.", "1.", "2." etc. until the
controller displays the quit screen "E"; now press the knob to quit.
In the case of menus 0 and 1, the user can view any parameter. For information about
menu 2, refer to Paragraph 4.3 RESET OPERATIONS 22. To set the parameters of me nu
3, refer to Paragraph 5.8 PROGRAMMING OF HYDRAULIC PARAMETERS 42. The other
menus are not for the User: the information in these menus is dealt with in the sections
dedicated to the installation technician or Robur TAC.
The special key allows the knob of the electronic board to be operated without opening
the cover of the electrical panel, so that operators are protected from live components.
When the necessary settings have been completed, put away the special key, replace the
cap on the aperture of the electrical panel and refit the front panel of the appliance.
4.3 RESET OPERATIONS
There are several possible reasons why the appliance may have error status and therefore
its operation arrested; such an error situation does not necessarily correspond to damage
or malfunction on the part of the appliance. The cause that has generated the error may
be temporary: for example, presence of air in the gas supply line or temporary power
failure.
The appliance can be reset with controller menu 2, the Comfort Control Panel (if present)
or the DDC (if present). In these two latter cases, refer to their documentation.
Reset appliance controller
The Table 4.3 Menu 2 22 shows the actions available in menu 2.
For regulatory reasons, the flame controller reset is in a dedicated voice of menu.
Table 4.3 – Menu 2
ACTION REQUIRED FOR EXECUTION SHOWN ON DISPLAY AS
0 Reset flame controller arrest 2. 0
1 Reset other operating codes 2. 1
3 Timed forcing to minimum power 2. 3
4 Timed forcing to maximum power 2. 4
5 Regulation of power 2. 5
E (EXIT MENU) 2. E
The general operating codes of the unit's controller can be reset with actions "0" and "1".
Actions "3", "4" and "5" are used to regulate the combustion parameters or for gas type
changeovers, and are thus for use only by the installation technician or Robur TAC (for
other information refer to Paragraph 7.1 PROCEDURE FOR FIRST START UP 73).
RESET FLAME CONTROLLER (ACTION "0"):
Reset flame controller arrest; this may be used when the appliance is first activated, see
Paragraph 4.1 START UP (AND SHUT DOWN) 17, when the appliance is in a permanent
locked condition or after a long period of disuse (see Paragraph 4.5 PROLONGED PERI-
ODS OF DISUSE 24).
You will need: access to the electrical panel, see Paragraph “Display and knob”.