Technical data
22
 In the same way: 7.  turn the knob to scroll through content (menus, parameters, ac-
tions), press the knob to select/confirm the content (access a menu, display/set 
a parameter, execute an action, quit or return to the previous level). For example, 
to quit the menus, turn the knob to scroll through menus "0.", "1.", "2." etc. until the 
controller displays the quit screen "E"; now press the knob to quit.
In the case of menus 0 and 1, the user can view any parameter. For information about 
menu 2, refer to Paragraph 4.3 RESET OPERATIONS → 22. To set the parameters of me nu 
3, refer to Paragraph 5.8 PROGRAMMING OF HYDRAULIC PARAMETERS → 42. The other 
menus are not for the User: the information in these menus is dealt with in the sections 
dedicated to the installation technician or Robur TAC.
The special key allows the knob of the electronic board to be operated without opening 
the cover of the electrical panel, so that operators are protected from live components. 
When the necessary settings have been completed, put away the special key, replace the 
cap on the aperture of the electrical panel and refit the front panel of the appliance.
4.3   RESET OPERATIONS
There are several possible reasons why the appliance may have error status and therefore 
its operation arrested; such an error situation does not necessarily correspond to damage 
or malfunction on the part of the appliance. The cause that has generated the error may 
be temporary: for example, presence of air in the gas supply line or temporary power 
failure.
The appliance can be reset with controller menu 2, the Comfort Control Panel (if present) 
or the DDC (if present). In these two latter cases, refer to their documentation.
Reset appliance controller
The Table 4.3 Menu 2 → 22 shows the actions available in menu 2.
For regulatory reasons, the flame controller reset is in a dedicated voice of menu.
Table 4.3 – Menu 2
ACTION REQUIRED FOR EXECUTION SHOWN ON DISPLAY AS
0 Reset flame controller arrest 2. 0
1 Reset other operating codes 2. 1
3 Timed forcing to minimum power 2. 3
4 Timed forcing to maximum power 2. 4
5 Regulation of power 2. 5
E (EXIT MENU) 2. E
The general operating codes of the unit's controller can be reset with actions "0" and "1".
Actions "3", "4" and "5" are used to regulate the combustion parameters or for gas type 
changeovers, and are thus for use only by the installation technician or Robur TAC (for 
other information refer to Paragraph 7.1 PROCEDURE FOR FIRST START UP → 73).
RESET FLAME CONTROLLER (ACTION "0"):
Reset flame controller arrest; this may be used when the appliance is first activated, see 
Paragraph 4.1 START UP (AND SHUT DOWN) → 17, when the appliance is in a permanent 
locked condition or after a long period of disuse (see Paragraph 4.5 PROLONGED PERI-
ODS OF DISUSE → 24).
You will need: access to the electrical panel, see Paragraph “Display and knob”.