Technical data
30
 FLOW REGULATION VALVE on the water inlet pipe (only if the appliance is control-•
led by a CCP/DDC).
 WATER FILTER installed on the water inlet pipe.•
 ISOLATION BALL VALVE on the water and gas pipes of the installation.•
 3 BAR SAFETY VALVE installed on the outlet water pipe.•
 PLANT EXPANSION TANK installed in the appliance outlet water pipe.•
 EXPANSION TANK for the individual appliance, installed on the water outlet pipe •
(primary  side).  Provide a  plant expansion  tank  in  any case (secondary side),  in-
stalled in the water outlet pipe.
The appliance is not equipped with an expansion tank; therefore it is necessary to install 
a suitable expansion tank, sized for the maximum temperature range and maximum op-
erating water pressure of the plant.
 variable rate WATER CIRCULATION PUMP, FOR PLANT WITH A SINGLE APPLIANCE, •
located on the water inlet pipe of the appliance, flowing towards the appliance.
 variable rate WATER CIRCULATION PUMP, FOR PLANT WITH A SEVERAL APPLIANCES •
(each appliance have is pump), flowing towards the appliance.
 PLANT FILLING SYSTEM: if automatic filling systems are used, a seasonal check of •
the percentage of monoethylene glycol in the plant is recommended.
For other components to be installed in the system, refer to "Design Manual". For fur-
ther information or technical support in this regard, contact Robur S.p.A.'s Presales Office 
(tel.+39 035.888.111) or visite site www.robur.it.
The operations necessary for the First Activation or Regulation of the appliance must be 
carried out exclusively by an authorised Robur Technical Assistance Centre (TAC). These 
operations are described in Section 7 INITIAL ACTIVATION AND MAINTENANCE → 73.
The products' guarantee is void if initial activation is not carried out by a Robur TAC.
5.4   GAS SUPPLY
The  installation  of gas  supply  pipes  must  be  compliant  with  current  regulations  and 
norms.
The  gas  supply  pressure  must  be  in  the  range  given  in  Table  5.2  Network  gas 
pressure → 31.
Supplying gas to the appliance at pressures higher than those indicated above can dam-
age the gas valve, resulting in dangerous situations.
LPG systems must be equipped with a first stage pressure reducer close to the LPG stor-
age tank, in order to reduce the gas pressure to 1,5 bar, and a second stage pressure 
reducer, close to the unit, in order to reduce pression from 1,5 bar to the value in agree-
ment with the gas network pressure of the country of installation (see Table 5.2 Network 
gas pressure → 31).
Exemple for the Italian market: for the G30 gas, from 1,5 bar to 0,030 bar (30mbar); for the 
G31 gas, from 1,5 bar to 0,037 bar (37mbar).