Technical data

Installation, user and maintenance manual – GAHP-GS/WS
31
LPG may cause corrosion; piping and fitting materials must be resistant to this
corrosion.
Vertical gas pipes must be equipped with a siphon and provided with a drain for the con-
densate that may form inside the pipe during cold periods. It may also be necessary to
insulate the gas pipe to prevent the formation of excessive condensate.
In any case, provide an isolation valve (ball valve) on the gas supply line, to isolate the
appliance when required.
Table 5.2 – Network gas pressure
E3-GS; E3-WS; E3-A; GAHP-GS; GAHP-WS; GAHP-A Gas supply pressure
Product categories Countries of destination G20 [mbar] G25 [mbar] G30 [mbar] G31 [mbar] G25.1 [mbar] G27 [mbar] G2,350 [mbar]
II
2H3B/P
AL, BG, CY, CZ, DK, EE, FI, GR,
HR, IT, LT, MK, NO, RO, SE,
SI, SK, TR
20 30 30
AT, CH 20 50 50
II
2H3P
AL, BG, CZ, ES, GB, HR, IE, IT,
LT, MK, PT, SI, SK, TR
20 37
RO 20 30
II
2ELL3B/P
DE 20 20 50 50
II
2Esi3P
FR 20 25 37
II
2HS3B/P
HU 25 30 30 25
II
2E3P
LU 20 50
II
2L3B/P
NL 25 50 50
II
2E3B/P
PL
20 37 37
II
2ELwLs3B/P
20 37 37 20 13
II
2ELwLs3P
20 37 20 13
I
2E(R)B ;
I
3P
BE 20 25 37
I
3P
IS 30
I
2H
LV 20
I
3B/P
MT
30 30
I
3B
30
For data regarding hourly fuel consumption of the appliance, refer to Tables 3.1 GS HT/LT
technical data 12 and 3.2 WS technical data 13.
5.5 CONDENSATE DISCHARGE
INDOORS UNITS
The fumes condensate outlet is on the left of the appliance.
The appliance is equipped with a siphon with a piece of pipe connected.
If you wish to use the pipe supplied with the unit, proceed as follows:
Connect the pipe to a plastic discharge manifold of the proper length.1.
The connection between the pipe and the manifold must remain visible.2.