Technical data

Installation, user and maintenance manual – GAHP-GS/WS
33
Reconnect the plastic pipe E and secure it with its clamp.5.
Fit the bottom left side panel.6.
If the appliance is operated with the siphon empty, there is a risk of leaks of exhaust flue
gas.
OUTDOORS UNITS
The fumes condensate outlet is on the left of the appliance.
The distance L between the coupling and the base may not exceed 110 mm.
The condensate discharge corrugated pipe, coming out from the side of the un-1.
derbase left support, must be connected to a proper discharge header.
The connection between the pipe and the manifold must remain visible.2.
Figure 5.4 – Position of condensate discharge outdoors units
Position of condensate discharge outdoors units
LEGEND
A Condensate discharge hose
D Corrugated hose
The condensate discharge to the sewer must be:
sized so as to discharge the maximum condensation flow (see Table 3.1 GS HT/LT •
technical data 12 and Table 3.2 WS technical data 13 under the respective
heading);
made of materials resistant to acidity with pH 3 to 5;•