Technical data
Installation, user and maintenance manual – GAHP-GS/WS
33
 Reconnect the plastic pipe E and secure it with its clamp.5. 
 Fit the bottom left side panel.6. 
If the appliance is operated with the siphon empty, there is a risk of leaks of exhaust flue 
gas.
OUTDOORS UNITS
The fumes condensate outlet is on the left of the appliance.
The distance L between the coupling and the base may not exceed 110 mm.
 The condensate discharge corrugated pipe, coming out from the side of the un-1. 
derbase left support, must be connected to a proper discharge header.
 The connection between the pipe and the manifold must remain visible.2. 
Figure 5.4 – Position of condensate discharge outdoors units
Position of condensate discharge outdoors units
LEGEND
A   Condensate discharge hose
D   Corrugated hose
The condensate discharge to the sewer must be:
 sized so as to discharge the maximum condensation flow (see Table 3.1 GS HT/LT •
technical data → 12 and Table 3.2 WS technical data → 13 under the respective 
heading);
 made of materials resistant to acidity with pH 3 to 5;•