Technical data
Installation, user and maintenance manual – GAHP-GS/WS
35
 Fill the hydraulic circuit to at least the minimum amount and add inhibited mo-3. 
noethylene glycol to a volume percentage in proportion to the minimum winter 
temperature in the installation area (see Table 5.3 Technical data for filling the hy-
draulic circuit → 36). Robur recommends using inhibited corrosion resistant mo-
noethylene glycol.
Glycol antifreeze may not be used on condition that the antifreeze function, which 
runs the circulation pumps, is activated at the CCI/DDC. This function requires the 
appliance to be ALWAYS powered up (electricity and gas) and power failures ex-
cluded, otherwise the manufacturer declines all  contractual and extra-con-
tractual liability for consequent damage.
 Check the filter on the return pipe for impurities; clean it if necessary.4. 
 Bring the plant to the correct pressure, making sure that the water pressure is not 5. 
less than 1 bar and not over 2 bar, and run the circu lation pump for at least 30 min-
utes. Check the water filter again and clean it if necessary.
The technical data (Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS technical da-
ta → 13) regarding the cold circuit refer to water with 25% glycol content, so that no 
correction factor need to be applied to Table 5.3 Technical data for filling the hydraulic 
circuit → 36.
To  facilitate  the  operation  of  bleeding  air  from  the  hydraulic  circuit,  the  appliance  is 
equipped with an additional manual air bleeding valve.
HOT CIRCUIT (Heating, sanitary hot water)
 Check that the system delivery and return are correctly connected to the appli-1. 
ance’s respective fittings (see Figure 3.1 Size → 15).
 Activate the automatic air purging valves of the plant and open all thermostatic 2. 
valves.
 Fill the hydraulic circuit to at least the minimum amount and add inhibited mo-3. 
noethylene glycol to a volume percentage in proportion to the minimum winter 
temperature in the installation area (see Table 5.3 Technical data for filling the hy-
draulic circuit → 36). Robur recommends using inhibited corrosion resistant mo-
noethylene glycol.
Glycol antifreeze may not be used on condition that the antifreeze function, which 
runs the circulation pumps and the appliance, is activated at the CCI/DDC. This 
function requires the appliance to be ALWAYS powered up (electricity and gas) and 
power failures excluded, otherwise the manufacturer declines all contractual 
and extra-contractual liability for consequent damage.
 Check the filter on the return pipe for impurities; clean it if necessary.4. 
 Check that the siphon on the condensate discharge has been filled with water as 5. 
indicated in  Paragraph 5.5  CONDENSATE DISCHARGE → 31 under "Loading the 
siphon".
 Bring the plant to the correct pressure, making sure that the pressure of the water 6. 
in the plant is not less than 1 bar and not over 2 bar, and run the circulation pump 
for at least 30 minutes. Check the water filter again and clean it if necessary.