Technical data

36
To facilitate the operation of bleeding air from the hydraulic circuit, the appliance is
equipped with an additional manual air bleeding valve.
Use of glycol antifreeze
Glycols, normally used to lower the freezing point of water, are substances in an inter-
mediate state of oxidation which, in the presence of oxidising agents such as oxygen,
are transformed into corresponding acids. This transformation into acids increases the
corrosive nature of the fluid contained in the circuit. For this reason, mixtures that are
commercially available almost always contain inhibiting substances that are able to con-
trol the pH of the solution. A condition necessary for the oxidation and degradation of
glycol is the presence of an oxidising agent such as oxygen. In closed circuits in which no
replenishment of water (and therefore of oxygen) occurs over time, once the oxygen ini-
tially present has reacted, the degenerative phenomenon of glycol is hugely inhibited.
Most circuits, however, are of the non-sealed type, and therefore receive a more or less
continuous supply of oxygen.
Therefore it is essential, whatever type of glycol is in question, to verify that it is ade-
quately inhibited and that the necessary checks are regularly performed during its entire
period of use.
Antifreeze liquids for cars, which do not contain inhibiting components other than ethyl-
ene glycol, are not recommended for cooling and heating plants.
The manufacturer does not accept any contractual or extra-contractual liability for
damages caused by the use or disposal of glycol antifreeze.
It is equally important to recall that the use of monoethylene glycol modifies the ther-
mophysical characteristics of the water in the plant, and in particular its density, viscosity
and average specific heat. Always check the date of expiry and/or degradation of the
product with the supplier.
The technical data (Tables 3.1 GS HT/LT technical data 12 and 3.2 WS technical da-
ta 13) regarding the hot circuit refer to non-glycolised water, so that the correction
factors of Table 5.3 Technical data for filling the hydraulic circuit 36 must be applied
to obtain the consequent increased load drop of the system and penalisation of unit ef-
ficiency in relation to the percentage of monoethylene glycol used.
Table 5.3 Technical data for filling the hydraulic circuit 36 should be taken into account
for the sizing of the pipes and the circulation pump (for calculation of internal pressure
drops of the appliance, refer to Tables 3.1 GS HT/LT technical data 12 and 3.2 WS tech-
nical data 13).
Nevertheless, it is advisable to consult the technical specifications of the monoethylene
glycol used. If automatic loading systems are used, a seasonal check of the quantity of
glycol present in the plant is also necessary.
Table 5.3 – Technical data for filling the hydraulic circuit
% of MONOETHYLENE GLYCOL 10 15 20 25 30 35 40
WATER-GLYCOL MIXTURE FREEZING TEMPERATURE -3°C -5°C -8°C -12°C -15°C -20°C -25°C
PERCENTAGE OF INCREASE IN PRESSURE DROPS -- 6% 8% 10% 12% 14% 16%
LOSS OF EFFICIENCY OF UNIT -- 0,5% 1% 2% 2,5% 3% 4%
If the percentage of glycol is ≥ 30% (for ethylene glycol) or ≥ 20% (for propylene glycol):
then parameter 182 in menu 4 must be set to “1” (at the installers care).•