Technical data

Installation, user and maintenance manual – GAHP-GS/WS
41
Figure 5.9 – C53 type installation
Double wall mounted exhaust
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in
Figure 5.9 C53 type installation 41
Table 5.8 – C53 type installation
DN Ref Description
80
B
Wall mounted terminal kit DN80C
D
F Pipe DN80 L=1 m
F Pipe DN80 L=2 m
G Bend 90° DN80
H Bend 45° DN80
Double wall mounted exhaust
Table 5.9 – Fumes temperature and flow
Gas type Thermal capacity CO
2
(%) TF (C°) Fumes flow (kg/h) Prevalenza residua (Pa)
G20
Nominal 9,10 65 42 80
Minimum 8,90 46 21 80
G25
Nominal 9,10 63,6 42 80
Minimum 8,90 45,7 21 80
G25.1
Nominal 10,10 65 45 80
Minimum 9,60 46 23 80
G27
Nominal 9,0 64 42 80
Minimum 8,5 46 21 80
G2.350
Nominal 9,00 62,7 42 80
Minimum 8,70 46,8 22 80
G30
Nominal 10,40 65 43 80
Minimum 10,10 46 22 80
G31
Nominal 9,10 65 48 80
Minimum 8,90 46 24 80