Technical data

58
The Comfort Control Panels power cord must be type tipo FG7 3Gx2.5mm1.
2
. the
power supply is 230V AC 1N 50Hz.
Cut a suitable length of cable.2.
The cable must be connected to the terminal block on the bottom right of the 3.
Comfort Control Panel. First make a hole in the electrical cabinet near to the termi-
nal block and pass the cable through it.
Connect the cable to the terminal block as given in Figure 6.6 Electrical wiring dia-4.
gram 50 and fit a 10 A thermal cut out upstream of the Comfort Control Panel.
How to connect the system water circulation pumps
Before making the electrical connections, make sure that work is not carried out on live
elements.
To optimise the operation of the appliance install, on the primary circuit, variable rate
WILO STRATOS PARA pumps (see Section 8 ACCESSORIES 81), which are controlled and
modulated with the Robur Mod10 controller.
No other models pump are supported.
The instruction for connecting the WILO STRATOS PARA pumps are given below (see Sec-
tion 8 ACCESSORIES 81).
Each WILO pump includes its power cord (length 1.5 metres) and cable for connection to
the appliances controller (1.5 metres). For longer cable runs, use a shielded 2x0.75 mm
2
0-10V signal cable and a FG7 3Gx2.5mm
2
power cord.
You will need: the appliance in its permanent location.
Check that power supply is off.1.
Remove the front panel of the appliance and the cover of the electrical panel.2.
Connect the brown wire of the WILO STRATOS PARA pump on the cold side to the 3.
terminal "-" of connector CPMP on the Mod10 board. Connect the white wire of the
WILO STRATOS PARA pump on the cold side to the terminal "+" of the connector
CPMP on the Mod10 board. Insulated black and blue wires (see Figure 6.14 Wiring
diagram for connection of Wilo variable rate pumps 59).
Connect the brown wire of the WILO STRATOS PARA pump on the hot side to the 4.
terminal "-" of connector HPMP on the Mod10 board. Connect the white wire of
the WILO STRATOS PARA pump on the hot side to the terminal "+" of the connector
HPMP on the Mod10 board. Insulated black and blue wires (see Figure 6.14 Wiring
diagram for connection of Wilo variable rate pumps 59).
Collegare la pompa alla rete elettrica prevedendo a monte un interruttore esterno 5.
bipolare (vedi particolare IP di Figura 6.14 Wiring diagram for connection of Wilo
variable rate pumps 59) con fusibile da 2 A ritardato oppure collegarla ai mor-
setti interni al quadro elettrico dell’unità (vedi particolare MA di Figura 6.15 Wiring
diagram for hooking up the Wilo variable rate pump powered by the unit 60).
After finished with all the above operations, close the electrical panel and refit the 6.
front panel of the appliance.
NEVER switch on or off the WILO STRATOS PARA pump through the switch on the power
supply.