63
 Roll the shielding and connect it to a 4-mm eyelet terminal, as illustrated in Figure 5. 
6.10 Connection from CAN BUS to connector P8 → 55, details C and D. Now pro-
ceed as follows:
 If the DDC is an 6.  terminal node connect the three coloured wires to the orange 
connector "P8", following the diagram provided in detail "A" of Figure 6.16 detail 
wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63. Observe the 
terminal markings L, H, GND (on the DDC at the base of the socket "P8") which are 
given both in Table 6.2 CAN BUS cables type → 51 and in the example.
 If the DDC is an 7.  intermediate node repeat the operations from step 2 to step 4 for 
the other length of CAN bus cable required. Connect the six coloured wires to the 
orange connector "P8", following the diagram provided in detail "B" of Figure 6.16 
detail wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63. Observe 
the terminal markings L, H, GND (on the DDC at the base of the socket "P8") which 
are given both in Table 6.2 CAN BUS cables type → 51 and in the example.
 Insert the orange connector ("P8") with the wires first into the opening prepared in 8. 
the cover of the DDC, and then into the appropriate socket on the DDC itself, mak-
ing sure it is correctly inserted.
 Use the rear cover bolts located near the CAN BUS socket to secure  the  4  mm 9. 
eyelet (or 2 eyelets) (detail D, Figure 6.10 Connection from CAN BUS to connector 
P8 → 55). The cable should be secured against pulling out.
Figure 6.16 – detail wires and jumpers J21 - terminal/intermediate node CCI/DDC
Detail terminal and intermediate node: jumpers position J21: "closed" - "open".
LEGEND
DDC   CCI/DDC
J21   Jumper CAN-BUS in CCI/DDC board
A   detail case "terminal node" (3 wires; J21=jumper "closed")
B   detail case "intermediate node" (6 wires; J21=jumper "open")
H,L,GND   data signal wires
How to connect the DDC
The DDC requires a low voltage power supply (24 V) with a 230/24 V AC, 50 Hz safety 
transformer;  the minimum power requirement is 20 VA. For the connection use a cable 
with the minimum specifications 2 x 0.75 mm
2
.