Technical data
Installation, user and maintenance manual – GAHP-GS/WS
67
 Direct control from the controller with power absorbed by the pump less than 700 •
W. If the power absorbed by the pump is less than 700 W, make the connection as 
shown in Figure 6.20 Electrical wiring diagram → 67 and check that the jumper J10 
and J1 are CLOSED, as shown in detail A.
 Direct control from the controller with power absorbed by the pump of more than •
700 W. If the power absorbed by the pump is more than or equal to 700 W, make 
the connection as shown in Figure 6.21 Electrical wiring diagram → 68 using a 
control relay. In this case it is necessary to OPEN the jumper J1 and J10 positioning 
its as shown in detail A and B of the Figure.
Figure 6.20 – Electrical wiring diagram
Connection of plant water circulation pumps (power absorption less than 700W), controlled directly by the appliance.
LEGEND
SCH   electronic board
SCH2   electronic board
J10   J1 - jumper closed
N.O. CONTACT   clean exit normally open
MA   Unit terminal block
L   phase
N   neutral
Components NOT SUPPLIED
PMW   Hot side water pump <700W
PMY   Cold side water pump <700W