Direct control from the controller with power absorbed by the pump less than 700 •
W. If the power absorbed by the pump is less than 700 W, make the connection as
shown in Figure 6.20 Electrical wiring diagram 67 and check that the jumper J10
and J1 are CLOSED, as shown in detail A.
Direct control from the controller with power absorbed by the pump of more than •
700 W. If the power absorbed by the pump is more than or equal to 700 W, make
the connection as shown in Figure 6.21 Electrical wiring diagram 68 using a
control relay. In this case it is necessary to OPEN the jumper J1 and J10 positioning
its as shown in detail A and B of the Figure.
Figure 6.20 – Electrical wiring diagram
Connection of plant water circulation pumps (power absorption less than 700W), controlled directly by the appliance.
LEGEND
SCH electronic board
SCH2 electronic board
J10 J1 - jumper closed
N.O. CONTACT clean exit normally open
MA Unit terminal block
L phase
N neutral
Components NOT SUPPLIED
PMW Hot side water pump <700W
PMY Cold side water pump <700W