Technical data
68
Figure 6.21 – Electrical wiring diagram
Connection of plant water circulation pumps (power absorption equal or more than 700W), controlled directly by the appliance.
LEGEND
SCH   electronic board
SCH2   electronic board
J10   J1 - jumper open
 N.O. CONTACT   clean exit normally open
MA   Unit terminal block
L   phase
N   neutral
Components NOT SUPPLIED
PMW   Hot side water pump ≥700W
PMY   Cold side water pump ≥700W
KPW   Hot side pump control relay
KPY   Cold side pump control relay
If several appliances are connected on the same hydraulic circuit, it is always necessary 
to provide a safety transformer (secondary SELV) and a respective control relay; make the 
connections according to the diagram in Figure 6.22 Electrical wiring diagram → 69.