Technical data
70
The primary circulation pump/s must be controlled by the S61 board, or directly 
(via “N.O. contact” contacts or 0-10V signal) or indirectly (“OR” use of said contacts 
by BMS type external systems). Otherwise, the primary circulation pump/s must be 
running permanently.
6.5   TYPE C CONSENT SWITCH
Before making the electrical connections, make sure that work is not carried out on live 
elements.
General indications
 Check that the power supply voltage is 230 V 1N - 50 Hz power.•
 Make the electrical connections as given in the following wiring diagrams.•
 Make the electrical connection in such a way that the ground wire is longer than •
the live wires. In this way it will be the last wire to be pulled away if the mains cable 
should accidentally be pulled, and will thus guarantee the ground connection.
Electrical safety is ensured only when the appliance is correctly connected to an efficient 
grounding system, realized according to current safety regulations. Do not use gas pipes 
as grounding.
How to connect the consent switch
You will need: the appliance is not powered electrically (external master power switch 
set to OFF)
 Connect the permissive (on-off switch or ambient thermostat or timer, etc.) to ter-1. 
minals R and W on the appliance’s electronic board as shown in Figure 6.23 Electri-
cal wiring diagram → 70 (detail “CS”).
For the appliance to operate correctly, it is ALWAYS necessary to provide a consent switch. 
Do not use the general mains external circuit breaker («GS») to switch the appliance on 
or off.
Figure 6.23 – Electrical wiring diagram
electrical connections of ON/OFF command switch
LEGEND
SCH   Electronic board
R   Common
W   Terminal consensus warming
Components NOT SUPPLIED
CS   ON/OFF command switch
How to connect the system water circulation pumps
For how to connect the system pumps, see the section with this title in Paragraph 
6.4 TYPE B (DDC) → 60.










