Variable  flow  pumps WILO STRATOS  PARA  can  also be used (see Section  8  ACCESSO-
RIES → 81). In this case, for the electrical wiring of the  pumps, please refer to Figure 
6.14 Wiring diagram for connection of Wilo variable rate pumps → 59 and the relevant 
paragraph.
6.6   HOW TO RESET THE FLAME CONTROLLER FROM REMOTE
The flame controller reset can be controlled remotely by installing a button (not sup-
plied) to the flame controller inside the unit’s electrical panel.
Connect the button as instructed below.
You will need: the appliance disconnected from the electricity supply
 The cable required to connect the reset button must be 3x0.75mm1. 
2
.
 Cut a suitable length of cable.2. 
 Connect the cable to the blind terminals A (see Figure 6.24 Button connection for 3. 
flame controller reset → 72).
The blind terminals are hidden on the rightinside the cable tray. To extract them, remove 
the cover of the tray, slide the cables out of the provided slots, and carefully close the tray 
again.
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the 
cabling carefully before powering the unit.