Technical data
Installation, user and maintenance manual – GAHP-GS/WS
75
The type of gas for which the appliance is set up can be identified from the adhesive label 
located on the unit’s internal gas pipe (detail M, Figure 7.2 Gas changeover → 80).
The nozzles required to change the gas type to G30 and G31 are supplied together with 
the appliance.
During the first start-up procedure it is in any case necessary to:
 check the dynamic gas mains pressure•
 check and adjust the appliance’s combustion parameters•
You will need: the appliance connected to the gas and electricity supply: switched off 
and with the gas cock closed; front panel removed.
Check the dynamic gas mains pressure
 Connect  the  manometer  to  the  gas  intake  (see  detail  D,  Figure  7.1  Gas 1. 
valve → 75).
 Open the gas valve and check that the grid static pressure complies to the value 2. 
reported in Table 5.2 Network gas pressure → 31 (with a tolerance of ±15%).
If  the  static  mains  pressure  is  greater  than  50  mbar  DO  NOT  switch  on  the 
appliance!
 Give the consent signal for operation.3. 
 After some seconds of operation, check that the grid dynamic pressure complies 4. 
with the value reported in Table 5.2 Network gas pressure → 31 (with a tolerance 
of ±15%).
Figure 7.1 – Gas valve
Gas valve Honeywell VK 4115V
LEGEND
A   Plug
B   Key Torx TX40
C   screw adjustment CO2
D   gas pressure intake