Technical data
78
Table 7.1
GUIDELINES FOR THE PREVENTIVE MAINTENACE OPERATIONS
Check of the unit GAHP-A GAHP-GS/WS AY ACF GAHP-AR
Visually check of the general condition of the unit and of its air heat exchanger. 
(1)
√ √ √ √
Check the correct operation of the device used for monitoring the water flow √ √ √ √ √
Check the % value of CO
2
√ √ √
check gas pressure to the burners √ √
Check that the condensate discharge is clean (clear the condensate discharge hole of any blockages)
[If necessary, frequency of the maintenace operation must be increased]
√ √ √
Replace the belts after 6 years or 12,000 hours of operation √ √ √ √
Check/restore the pressure of the primary hydronic circuit √
Check/restore the air pressure inside of the expansion vessel of the primary hydronic circuit √
Check every CCI or DDC
(2)
DDC o CCI
Check that the plant is able to achive the setpoint temperature √
Download the hystorical events √
1   It is suggested the cleaning of the air heat exchanger once every 4 years [the optimal frequency of this operation is in any case a consequence of the installation site].
2   Check that the plant is able to achive the setpoint temperature.
ORDINARY SCHEDULED MAINTENANCE
Perform the following operations at least once every 2 years.
If the unit is subject to particularly heavy duty (for example in process plants or in 
other  conditions  of  continuous  operation),  these  maintenance  operations must  be 
more frequent.
Table 7.2
SCHEDULED MAINTENANCE OPERATIONS TO BE PERFORMED AT LEAST ONE EVERY TWO YEARS
Check of the unit GAHP-A GAHP-GS/WS AY ACF GAHP-AR
Clean the combustion chamber √ √ √ √ √
Clean the burner √ √ √ √ √
Clean the electrodes of ignition and flame sensing √ √ √ √ √
Check that the condensate discharge is clean (clear the condensate discharge hole of any blockages) √ √ √
Replace the silicone gasket √
In Section 5 HYDRAULIC INSTALLATION → 26 are reported suggestions related to the 
hydraulic plant.
7.3   CHANGE OF GAS TYPE
This operation must be carried out exclusively by an authorised Robur Technical Assist-
ance Centre (TAC).
If the appliance is to be used with a type of gas other than that indicated on the the adhe-
sive label located on the unit's electric panel, switch off the appliance, shut off its power 
and gas supplies and proceed as follows (see Figure 7.2 Gas changeover → 80):
You  will  need: the  appliance  switched  off  and  disconnected from  the  gas/electricity 
supplies
 Disconnect the gas pipe from the gas valve.1. 
 Undo the 4 bolts E shown in Figure 7.2 Gas changeover 2.  → 80 and remove the gas 
valve/blower assembly from the burner.
 Protect the burner from bolts and nuts falling into it.3. 
 Using a CH 4 hex key, undo the 4 bolts G indicated in Figure 7.2 Gas changeo-4. 
ver → 80 and remove the nozzle D from the gas valve.