9 OPERATING CODES/TROUBLESHOOTING
9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING
Table 9.1 – TABLE OF OPERATING CODES generated by the S61 electronic board (firmware version 3.024)
CODES DESCRIPTION TRIP CONDITIONS RESET METHOD
E 200
FAULT ON RESET CIRCUIT OF FLAME
CONTROL UNIT
Fault on reset circuit of flame control unit. Contact authorised Technical Assistance.
u 201
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
High temperature detected by limit thermostat
on body of generator
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 201
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
u_01 code active for 1 hour, or u_01 code
generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 202 FUMES THERMOSTAT
High temperature detected by exhaust fumes
thermostat.
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 202 FUMES THERMOSTAT
u_02 code active for 1 hour, or u_02 code
generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 203
COLD WATER ANTIFREEZE
THERMOSTAT
Low temperature detected by cold outlet water
sensor.
Reset occurs automatically when the condition that generated the
code ceases, with hysteresis of 2 °C.
E 205 HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient
temperature sensor.
Reset occurs automatically when the condition that generated the
code ceases.
u 206 LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient
temperature sensor.
Reset occurs automatically when the cause ceases or when the unit
is switched off.
u 207
HIGH CONDENSER INLET
TEMPERATURE
Temperature measured by condenser inlet sensor,
fumes sensor or generator fin sensor HIGH.
Reset occurs automatically when the condition that generated the
code ceases.
E 207
HIGH CONDENSER INLET
TEMPERATURE
u_07 code active for 1 hour, or u_07 code
generated 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 1). If the
code persists, contact authorised TAC.
E 208 FLAME CONTROL UNIT ERROR
E_12 on unit and condenser inlet temperature
increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 1). If the
code persists, contact authorised TAC.
u 210 INSUFFICIENT COLD WATER FLOW
Insufficient water flow (the circulator is on and
the flowmeter is open).
Reset occurs automatically when correct water flow is restored.
E 210 INSUFFICIENT COLD WATER FLOW
u_10 code generated 5 times since appliance
powered, or code u_10 is active for 1 hours.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
u 211
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
Insufficient rotation of oil pressure pump. Reset occurs automatically 20 minutes after the Code is generated.
E 211
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
u_11 code generated twice in 2 hours of
operation.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
u 212 FLAME CONTROL UNIT ARREST Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again
(new ignition attempt), or if the code persists for 5 minutes.
E 212 FLAME CONTROL UNIT ARREST Flame arrest signal.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 0). If the code persists, contact authorised
TAC.
E 216
COLD OUTLET WATER
TEMPERATURE SENSOR DEFECTIVE
Fault (interruption or short circuit) on outlet water
temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 217
COLD INLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser
outlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 220
CONDENSER INLET TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser
inlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 222 WATER FLOWMETER FAULT Water flowmeter fault.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 223 AIR/GAS MIXTURE SENSOR FAULT Air gas mixture sensor fault.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 224
FUMES TEMPERATURE SENSOR
FAULT
Fumes temperature sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 225
CONDENSATE DISCHARGE
CLOGGED
Condensate discharge clogged
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 226
GENERATOR FIN TEMPERATURE
SENSOR
Generator fin temperature sensor
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 228
GAS SOLENOID VALVE EXCITED
DURING FLAME CONTROLLER
ARREST
The flame controller is arrested (E_12) but the gas
solenoid valve is excited. In this case the flame
controller is de-excited (E_12 resets).
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
u 229
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Gas solenoid valve is off for 5 seconds (with
central flame control unit on).
Reset occurs automatically if the gas solenoid valve switches on
again within 10 minutes (with central flame control unit on).
E 229
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Code u_29 is active for more than 10 minutes
(with flame controller unit on).
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 1). If the
code persists, contact authorised TAC.