Owner's manual
1305 Dynamic Brake 11
1305-5.11 May, 1999
BULLETIN 1305
DB Enable
Parameter 11
GND GND L1
R1
L2
S
L3
T
+DC BRK
(-DC)
TI
U
T2
V
T3
W
1305 BRAKE
BRK GND +DC
Terminal Block Wiring
Capacity
Screw Size, Wire Size and Torque Specifications.
Terminal Screw Size Maximum/Minimum Wire Size Maximum Torque
TB1 M4 4/0.75 mm (10/18 AWG) 1.81 N-m (16 lb-ins.)
Setup
ATTENTION: The dynamic brake unit contains a
thermostat to guard against overheating and component
damage.
If the duty cycle, torque setting and/or ambient temperature
exceeds the specifications listed in this publication, the
thermostat is designed to trip and disable the brake.
If reduced braking torque represents a potential hazard to
personnel, auxiliary stopping methods must be considered in
the machine and/or control circuit design.
!
P.011 — Set DB Enable to Enable
This parameter must be set to enable when dynamic braking is
installed. Refer to your 1305 User Manual for programming
procedures and record the changes for future reference.
Wiring Scheme