User Manual
6–30 Parameters
Publication 1336 FORCE–5.18 ––March, 1999
404
Analog Output 3 Offset
[Analog Out 3 Offset]
Analog Out 3 Offset determines the offset applied to
the Analog Out 3 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number 404
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Output
405
Analog Output 3 Scale
[Analog Out 3 Scale]
Analog Out 3 Scale determines the scale factor or
gain for the Analog In 3 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 3 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor Drive Units
1 32767
1/2 16383
1/4 8192
1/16 2048
Parameter Number 405
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –1
Maximum Value +1
File – Group Communication I/O – Analog Output
406
Analog Output 4 Offset
[Analog Out 4 Offset]
Analog Out 4 Offset determines the offset applied to
the Analog Out 4 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number 406
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Output
407
Analog Output 4 Scale
[Analog Out 4 Scale]
Analog Out 4 Scale determines the scale factor or
gain for the Analog In 4 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 4 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor Drive Units
1 32767
1/2 16383
1/4 8192
1/16 2048
Parameter Number 407
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –1
Maximum Value +1
File – Group Communication I/O – Analog Output