Local and Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 3
3-4
Parameter 5  Frequency Select 1
Freq
P
R
P
R
Enter
Code
0
5
0
Read and Write
Units
Minimum Value
Maximum Value
Factory Setting
This parameter selects one of six possible sources to control drive output
frequency when TB3 Terminal 27 is false. Either:
0 A Control Panel speed potentiometer
1 A 0 to +10V DC source at TB2
2 A 4 to 20mA source at TB2
3 A pulse train source at TB2
4 A serial input source from 1336-MOD-G2 at the serial input port
connector if 1336-MOD-S1 is installed.
5 A remote speed potentiometer connected to TB2 Terminals 1, 2 & 3.
In addition to the selected parameter, other drive inputs may alter the
source used for frequency control. Other sources include:
Jog — Parameter 24
Preset Frequency 1 — Parameter 27
Preset Frequency 2 — Parameter 28
Preset Frequency 3 — Parameter 29
This parameter may be programmed to only one of the six selectable values
listed, 0 – 5. Whenever Parameter 5 is selected, a value of 0 – 5 will be
displayed. Since other sources can be the control source, the Operating
Display however will always show the frequency source using the
following code:
0 Control Panel speed potentiometer
1 0 to +10V DC input
2 4 to 20mA input
3 Pulse train input
4 Serial input
5 Remote speed pot input
6 Jog
7 Preset Frequency 1
8 Preset Frequency 2
9 Preset Speed 3 or if Parameter 72 is set to 1, Preset Speeds 4-7.
Use the information provided in the 1336VT User Manual to determine
what will be the drive speed source for various conditions.